Laserfiche WebLink
s <br /> .� ITTS Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> January 5 , 1988 <br /> Stockton Service Stations �. <br /> Equipment Company <br /> P. 0. Box 508 <br /> Stockton, California 95201 APR 211989 <br /> Site : Mobil Corporation <br /> 3505 Navy Drive <br /> Stockton, California P� <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gal !.ons per one hour of testing . If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Behind 6 ,000 Water +.009776 Yes <br /> #216 <br /> T!`?.easc! contact us if you reed additional assistance or <br /> informat Lou . <br /> Sincerely , <br /> ��-Z- <br /> 1 <br /> W. Savage <br /> Certified Tester <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />