Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: x Tank Manufacturer ❑Industry Standard 0 Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure x Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Dwyer Manometer Equipment Resolution:+/-2% <br /> Tank# 1 Tank# Tank# Tank# <br /> [is Tank Exempt From Testing?' ❑Yes x No ❑Yes ❑No 0 Yes 0 No 0 Yes D No <br /> Tank Capacity: 10,000 <br /> Tank Material: Fiberglass <br /> Tank Manufacturer: Unknown <br /> Product Stored: Waste Water <br /> Wait time between applying <br /> pressure/vacuum/water and 30 min 30 min 30 min 30 min <br /> starting test: <br /> Test Start Time: 10:00 <br /> Initial Reading(RI): 8.35 <br /> Test End Time: 11:00 <br /> Final Reading(RF): 8.33 <br /> Test Duration: 1 hour 1 hour I hour 1 hour <br /> Change in Reading(RF-Rl): .02 <br /> Pass/Fail Threshold or Criteria: No less than 1" No less than I" No less than 1" No less than 1" <br /> Test Result: x Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? x Yes ❑No ❑NA x Yes ❑No ❑NA x Yes ❑No ❑NA x Yes ❑No ❑NA <br /> Was sensor properly replaced and x Yes ❑No ❑NA x Yes ❑No 0 NA x Yes ❑No ❑NA x Yes ❑No. ❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> tPetin�r 1('alifnmia('-Al of Rrrti,latinnc Titles TI QPrtinn 14'1'71al!(ill <br />