Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for KWIK SERV LODI BW 113 * as of October 07 , 2020 . <br /> Open violations from January 09 , 2020 inspection <br /> ❑ This violation was corrected ❑ This violation will be corrected by (date ) : <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Violation #319 Failure to comply with the installation , inspection , or record keeping of the overfill <br /> prevention . <br /> OBSERVATION : The mechanical flapper used as the overfill prevention system on the 87 and diesel UST was <br /> listed as a failure on the 4/17/ 19 overfill prevention equipment inspection and is not currently functional . <br /> REGULATION GUIDANCE : All UST systems must be equipped with an approved , functional overfill prevention <br /> device at all times during delivery operations . <br /> CORRECTIVE ACTION : Immediately discontinue deposition of petroleum into this tank until the component is <br /> repaired or replaced by a properly licensed , trained , and certified contractor under permit and inspection of the EHD . <br /> If the failed component can 't be replaced immediately , there is a possibility that the [GRADE] UST system may be <br /> red tagged to prevent fuel inputs . <br /> IN This violation was corrected ❑ This violation will be corrected by ( date) : <br /> ❑ Supporting documents included ` - <br /> Describe actions taken or will be taken to correct violation : r� IeC � ,� �1 <br /> Page 3 of 3 <br />