Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> i , �V <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> KWIK SERV LODI BW 113* 420 W KETTLEMAN LN, LODI January 09, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 206 CCR 2712 Failure to comply with UST operating permit conditions. <br /> OBSERVATION:According to the replacement notifications sent to EHD on 9/10/2019 and 11/1/2019, the 87 <br /> product leak detector was replaced on 9/9/2019 and the 91 product leak detector was replaced on 10/27/2019;work <br /> orders or testing documentation indicating the replacement were not found on site at the time of the inspection. <br /> REGULATION GUIDANCE: Emergency repairs relating to UST system monitoring and release detection may be <br /> performed by a properly licensed,trained, and certified contractor pursuant to the EHD's policy and a permit <br /> obtained within one business day from the EHD. All other repairs must have a permit submitted to and approved by <br /> the EHD prior to beginning work. <br /> CORRECTIVE ACTION: Immediately obtain a permit from the EHD for the replacement of the leak detectors on the <br /> 87 and 91 tanks. A"Failure to Obtain a Permit" penalty applies. <br /> This is a minor violation. <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> 1)OBSERVATION:The designated operator failed to check and note the correct test dates for the Secondary <br /> Containment Testing on the 1/2019-1-2020 designated operator inspection reports. Secondary Containment <br /> Testing was conducted on 1/16/2018. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> 2)OBSERVATION: Designated operator reports were not signed within the required time frame. <br /> -The 1/11/2019 designated operator report was not signed by the owner/operator. <br /> REGULATORY GUIDANCE:Within 48 hours of the completion of the designated UST operator visual inspection, <br /> the designated operator shall sign and provide the owner or operator with a copy of the inspection report. Within 48 <br /> hours of being provided a signed copy of the report,the owner or operator shall provide a description of each <br /> corrective action taken or to be taken and shall sign and date the report, acknowledging the identified compliance <br /> issues. <br /> CORRECTIVE ACTION: Ensure all designated operator inspection reports are completed and signed within the <br /> required time frame in the future. <br /> This is a minor violation. <br /> FA0003776 PR0231906 SCO01 01/09/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />