Laserfiche WebLink
rings . Also replaced worn product relay. Tested new MLD with VMI tester . Test passed . 91 grade line now holding good <br /> at 32 PSI . No more slow flow issues found . <br /> -- Oct 24 2019 11 : 10AM - MSMITH -- I <br /> Cashier said slow flow issue was with the 91 grade and mechanic said problem was with the 87 grade . Tested 87 grade <br /> all ok . Line pressure holding ok and MLD working probably . Tested 91 grade and was able to duplicate slow flow issue <br /> caused by MLD . Found line pressure dropping slowly and MLD not resetting right away . Need to order MLD, check valve <br /> and o ring kit for 91 grade turbine . <br /> Thanks, <br /> Maria <br /> From : Monica Farhat [ mailto : mfarhat(aboyett . net] <br /> Sent : Monday, December 28, 2020 9 : 40 am <br /> To : Maria Guarnelli <br /> Subject : RE : Overfill test results <br /> Good morning Maria , <br /> Have you had a chance to look up the overfill prevention test results for 87 and diesel for the Kwik Sery in Lodi ? 420 W . <br /> Kettleman Ln , Lodi . <br /> I also need the service report for the replacement of the leak detectors for 87 and 91 in the months of September and <br /> November 2019 . The inspector was not able to locate the service report onsite , she is requesting a copy for the work . <br /> Let me know if you have any questions . I appreciate you taking the time to send these reports to me . <br /> Thank you , <br /> lMonica ,Farhat <br /> Operations & Compliance <br /> Boyett Petroleum <br /> (209) 495- 6243 <br /> mfarhat@boyett. net <br /> PB BOYETT <br /> MMLIEum <br /> z <br />