/ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> LAW Tanknology Line Leak Detector Test <br /> Work Order: 2343353 Date: 1/10/2020 <br /> Site Name/ID: CHEVRON#201383(N-2515-1-1)/201383 <br /> Address: 1960 W. 11TH STREET @ CORRAL HOLLOW <br /> City: TRACY State: CA Zip: 95376 <br /> Tank ID T2 T1 T3 <br /> Product REGULAR SUPREME Diesel <br /> Product Line 1 1 1 <br /> Tested From 11 11 11 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD <br /> Serial No. 385967 385959 385974 <br /> Pump Operating Pressure(psi) 39.00 36.00 40.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI <br /> 'NIA for Electronic LD's <br /> Resiliency(ml) <br /> 'N/A for Electronic Lo's <br /> Metering PSI <br /> 'N/A for Electronic LD's <br /> Opening Time(sec) <br /> 'N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: /° Expire Date: 1/27/2022 <br /> Environmental Compliance for Petroleum Systems <br /> ©2020 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />