c� <br /> The following is an itemized list of underground storage tank violations 4%71haC-re Dot f <br /> been addressed for 99 SHELL* as of March 27, 2017. <br /> Open violations from August 24, 2016 inspection <br /> Violation #305 -VPH monitoring of the interstitial spaces of the UST system is not maintained. <br /> Communication in under dispenser containment(UDC) 5/6 failed when tested. The interstitial space of UDC 5/6 sha <br /> be maintained, as designed, under constant vacuum such that a breach in the primary or secondary containment is <br /> detected before the hazardous substance is released into the environment. Communication in the 87-, 91-, and <br /> diesel product fill sumps, as well as vacuum sensor monitoring of the secondary containment piping of the <br /> vacuurn1pressure/hydrostatic(VPH) system were not tested during the inspection today. The interstitial space of the <br /> UST shall be maintained, as designed, under constant vacuum such that a breach in the primary or secondary <br /> containment is detected before the hazardous substance is released into the environment. Immediately contact a <br /> properly licensed, trained, and certified contractor to test communication of the VPH components listed above under <br /> inspection by the Environmental Health Department(EHD). <br /> Page 1 of 1 <br />