Laserfiche WebLink
Environmental Health Department <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> 99 SHELL" 1 7700 MORELAND ST, STOCKTON September 06, 2018 <br /> UST System Observations <br /> 319 CCR 2635(b) No spill bucket,failed to contain five gallons,or failed to provide a means to keep it empty _V ❑R ❑COS <br /> 320 CCR 2635(b)(2) Overfill prevention system not present or failed to meet overfill requirements V ❑R ❑COS <br /> 321 CCR 2635(b)(2) Overfill prevention was overridden ❑V ❑R ❑COS <br /> 322 HSC 25281.6(a) Unburied below grade emergency generator system failed to meet exemption status ❑V ❑R ❑COS <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status ❑V ❑R ❑COS <br /> 324 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V ❑R ❑COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored ❑V ❑R ❑COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements ❑V ❑R ❑COS <br /> 329 HSC 25298 Failed to comply with all permanent closure requirements ❑V ❑R ❑COS <br /> 330 CCR 2636(f)(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system ❑V ❑R ❑COS <br /> 331 CCR 2630(d) Secondarily contained piping not maintained to allow liquid to drain into sump ❑V ❑R ❑COS <br /> 332 CCR 2631(b),2631(d) Primary and/or secondary containment not constructed in accordance with the established standards L:V ❑R o COS <br /> Single-Walled Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve ❑V ❑R ❑COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V ❑R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS Il, or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 316 HSC 25290.1(c3), 25290.2(c3) Secondary containment not constructed to prevent water intrusion (after Jul 2003). <br /> No water tight sump shield, shroud boots, or clamps were available for the newly installed 91 Fill sump, also, no <br /> above components were present on the 87, or diesel fill sumps. Mr. Angle indicated that these components were <br /> never installed and he was not told by the prior inspectors that these components are required. Secondary <br /> containment shall be constructed to prevent any water intrusion into the system by precipitation, infiltration, or <br /> surface runoff. Contact a properly licensed, trained, and certified contractor to address the secondary containment <br /> construction deficiencies at this site. <br /> This is a repeat violation, Class ll. <br /> Overall Inspection Comments: <br /> Onsite for a billable reinspection to address some of the items not tested due to repairs involving 91 Fill Sump <br /> (SR0079123) during the routine monitoring system certification conducted on 8-30-2018. The following items <br /> were tested today: <br /> FA0003732 PR0231819 SC333 09/06/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 3 of 4 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />