<br /> Aboveground Petroleum Storage Act Inspection Report
<br /> Facility Name: I Facil it,Address: Oate:
<br /> BROWN SAND INC 800 WMOSSCALEAVE, LATHROP February 04, 2020
<br /> SUMMARY OF VIOLATIONS
<br /> (CLASS I,CLASS II,or MINOR-Nmicem Comply)
<br /> Item M Remarks
<br /> 710 CFR 112.8(cx6)Plan failed to adequately discuss procedures to test or inspect each container for integrity.
<br /> The SPCC plan does not determine, in accordance with industry standards,the appropriate qualifications for
<br /> personnel performing tests and inspections,the frequency and type of testing and inspections,which take into
<br /> account container size,configuration, and design.The SPCC plan calls for integrity testing double walled tanks to
<br /> be performed every two years by a licensed tank testing company and in accordance with manufactures
<br /> recommendations.The SPCC plan does not reference an industry standard for the integrity testing of the tanks.A
<br /> Periodic Integrity Testing Certificate was presented for the tanks,which was dated April 2017,per the SPCC plan an
<br /> itegrity test should have been conducted within two years.An integrity test has not been conducted within the last
<br /> two years.
<br /> Test or inspect each aboveground container for integrity on a regular schedule and whenever you make material
<br /> repairs.You must determine,in accordance with industry standards,the appropriate qualifications for personnel
<br /> performing tests and inspections,the frequency and type of testing and inspections,which take into account
<br /> container size,configuration,and design (such as containers that are:shop-built,field-erected,skid-mounted,
<br /> elevated,equipped with a liner,double-walled,or partially buried).Examples of these integrity tests include, but are
<br /> not limited to:visual inspection,hydrostatic testing, radiographic testing, ultrasonic testing,acoustic emissions
<br /> testing,or other systems of non-destructive testing.You must keep comparison records and you must also inspect
<br /> the container's supports and foundations. In addition, you must frequently inspect the outside of the container for
<br /> signs of deterioration,discharges, or accumulation of oil inside diked areas. Records of inspections and tests kept
<br /> under usual and customary business practices satisfy the recordkeeping requirements of this paragraph.
<br /> The SPCC plan mat address in accordance with industry standards,the appropriate qualifications for personnel
<br /> performing tests and inspections,the frequency and type of testing and inspections,which take into account
<br /> container size,configuration,and design or an environmental equivalence as allowed by CFR 112.7(ax2).Changes
<br /> to this section will require a certification by a Professional Enginee.
<br /> This is a Class II violation.
<br /> Overall Inspection Comments:
<br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement
<br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting
<br /> paperwork, by March 5, 2020.
<br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate($152). To schedule an
<br /> appointment, please call (209)468-3420.
<br /> The following was provided during this inspection: Schedule of free CU PA classes,
<br /> FM010S. PROSIU83 50301 0290.2021
<br /> E11)18U1 Rcr.&2N1019 Page 7 of AIaA,,JPtl eum Sbra)e AC OIR
<br /> 1868 E. Hazelton Avenue I Stockton,California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjoehdCom