Laserfiche WebLink
HVAC SYSTEM REPORT 1/2/13106 <br /> =MacArthur <br /> SYSTEM SUMMARY DATA: FAN NAMEPLATE DATA: <br /> FAN: DESIGN ACTUAL MANUFACTURER CENTRAL BLOWER CO.EXHAUST AIR CFM -1885 -1852 MODEL RE-15 <br /> RETURN AIR CFM - - TYPE ROOF EXHAUST <br /> OUTSIDE AIR CFM - SIZE SYSTEM: <br /> FAN RPM 1615 SERIAL NUMBER RF-3085 <br /> STATIC PRESSURE+ - - FAN PULLEY DATA: HOOD - 1 <br /> STATIC PRESSURE- DIAMETER 4-5/8" EF - 1 <br /> TOTAL STATIC PRESSURE - ;CLEAN <br /> SHAFT 1 <br /> FILTER STATIC PRESSURE ADJ/FIXED FIXED <br /> MOTOR: MOTOR PULLEY DATA: READINGS BY: <br /> MPS 3.4-3.7 DIAMETER 4-114" <br /> OLTS/PHASE 208-230/3 SHAFT 518•• DM & TU <br /> HORSEPOWER 1 ADJ/FIXED ADJ <br /> _ RPM 1725 1730 BELT NO. & SIZE (1)AP47 <br /> MOTOR NAMEPLATE DATA: JOB NUMBER: <br /> TEMPERATURE IN: - MANUFACTURER BALDOR <br /> TEMPERATURE OUT: - VOLTS/PHASE 208-230/3 261231 <br /> DROP/RISE: - HORSEPOWER 1 <br /> MODE: - FULL LOAD AMPS 3.4-3.7 <br /> RPM 1725 LjLj <br /> REMARKS: SERVICE FACTOR 1.15 <br /> -All readings for grease filters are from EXHAUST DUCT SHAFT: <br /> left to right. SIZE 12"x12" Q � <br /> AREA 1.0 Sq.Ft. rn <br /> VELOCITY (FPM) 1852 o 00 <br /> (Velocity must be between 1500-2500 FPM) Q LOco <br /> M Lo CV <br /> DIFFUSERS AND GRILLS W w .0 <br /> Room Outlet Code Size Required Test 1 Final % o Cr) Z rn <br /> Q ( <br /> No, CFM Velocity/CFM Velocity/CFM Design 11:3eX or O <br /> Hood 1 1 Filter 13.25XI2.25 - -276/-309 -293/-328 � O O <br /> Hood 1 2 Filter 13.25•x12.5• - -2881-331 -306/-352 V_ Y] J X <br /> Hood 1 3 Filter 13.25•xi2.75 - -3221-377 -3661-428 Z d O <br /> Hood 1 4 Filter 13.25•x13•• - -301/-361 -3381-406 LLl <br /> Hood 1 5 Filter 3.25 x13 264/-317 -282/-338 O <br /> 00 <br /> TOTAL -1885 -1695 -1852 98% O = <br /> � d <br /> V � <br /> W <br /> a <br />