Laserfiche WebLink
• Soil Sampling Report - Underground Storage Tanks <br /> Name of Business Ekholm Property <br /> Site Address 1702 Jackson Street, Escalon, California <br /> Type of Work Performed Soil samples taken for laboratory testing during over- <br /> excavation of former underground storage tank pits <br /> Date Sampled January 4, 1994 <br /> Number of Tanks Removed Six USTs were removed in 1991 <br /> No of Tanks - Capacity. Contents, Type. Condition <br /> 1 - 550 gallon diesel <br /> 2 - 2,000 gallon gasoline <br /> 1 - 4,000 gallon gasoline <br /> 1 - 10,000 gallon gasoline <br /> 1 - 350 gallon waste oil <br /> Soil Samples <br /> Sample ID Depth (ft) Location Description/Soil Description <br /> EXF1-13' 13' From floor of former diesel tank pit, adjacent to north wall, <br /> orange, medium-coarse sand, moist, no product odor <br /> EXNW-8' 8' Center of north wall of former diesel tank pit, gray, medium- <br /> coarse sand, moist, strong diesel odor <br /> EXEW-8 5' 8 5' North-center of east wall of former diesel tank pit, red-orange <br /> clayey sand, moist, slight diesel (9) odor <br /> EXSW-11' 11' Center of south wall of former diesel tank pit, red-orange sand, <br /> minor clay, moist, no product odor <br /> EXWW-14 5' 14 5' Northwest corner of west wall of former diesel tank pit, orange <br /> silty sand, moist, no product odor <br /> • EXWOF-9 5' 9 5' From floor of former waste oil tank pit, red-orange sand with <br /> gravel and clay, no product odor <br /> 1500471SSR-0194 FNL <br /> 1 <br />