Introduction System Description <br /> • Red Jacket, Tokheim, or Bennett Pumps Using <br /> PLLD SwiftCheck Valve <br /> The PLLD System with the SwiftCheck Valve option for use with Red Jacket, <br /> Tokheim,or Bennett pumps(Form No. 848480-003)contains the items in Table 4: <br /> Table 4.PLLD System with Red Jacket, Tokheim,or Bennett Pumps (SwiftCheck Valve) <br /> Quantity Description <br /> 1 Line Leak Sensor <br /> 1 SwiftCheck Valve <br /> 10 WARNING Tags <br /> Several Epoxy Packs,Wire Nuts,and Watertight Cord Grip <br /> 1 Site Preparation and Installation Manual <br /> PLLD Operation with an FE Petro Variable Speed Pump <br /> For satisfactory PLLD operation with an FE Petro variable speed pump,you need to: <br /> ❑ Change the settings of the dip switches <br /> ❑ Use specific rotary switch positions <br /> Dip Switches <br /> Change the factory settings of dip switches 1 or 2 or both from the on/on position to <br /> any combination of settings other than on/on or off/off[Table 5]. <br /> Table 5.Dip Switch Settings <br /> Pole 1 Pole 2 <br /> ON OFF <br /> OFF ON <br /> Important If the factory settings are not changed,the system will not detect leaks less than <br /> 3.0 gph. In this situation,the system will always pass 0.1 gph tests,but the results will <br /> not be valid. <br /> 576013-902,Revision G 7 <br />