Laserfiche WebLink
System Checkout Checking the System <br /> a. From the All Functions Normal operating screen,press FUNCTION to <br /> display the message: <br /> START LINE PRESSURE TEST , <br /> PRESS<STEP>TO CONTINUE <br /> b. Press STEP.The system displays the message: <br /> SELECT LINE <br /> RLL LINES <br /> c. To test all lines,proceed directly to step d.To test a single line,first press <br /> CHANGE.The system displays the message: <br /> SELECT LINE <br /> Q#: PLLO NUMBER # <br /> To test a different line,press CHANGE until the desired line is displayed. <br /> d. Once you have selected the lines to be tested,press ENTER or STEP. <br /> Depending on your choice in the preceding step,the system displays either of <br /> the following messages: <br /> STRRT LINE TEST: RLL LINES STRRT LINE TEST: LINE W <br /> PRESS<ENTER> PRESS<ENTER> <br /> e. Press ENTER to begin the test.The system displays the message: <br /> Q #: RUNNING PUMP <br /> PRESS <STEP>TO CONTINUE <br /> f. During testing,the system displays the message: <br /> Q #: TESTING 3.0 GRUHR <br /> Importantow If the console has been programmed to run a 0.1 gph test, after completing the 3.0 gph <br /> test the system will automatically begin testing at 0.1 gph. The 0.1 test may be <br /> interrupted or not completed and the dispensers will still dispense. A 3.0 gph test must <br /> be passed before the dispensers can be used for that product line being tested. <br /> g. When the test is done,the system displays the message: <br /> Q #: TEST COMPLETE <br /> h. To exit this function or cancel the test,press STEP. <br /> 40 576013-902, Revision G <br />