Laserfiche WebLink
Test Date: 03/14/2006 <br /> + 7bn;avo gy Work Order: 2241293 <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SUMP TESTS <br /> Tank or Disp Model or Diam. dlh/Length Oepth Test Method Start Initial Level Finish Final Pass/ <br /> Tye Manufacturer Time Level Change Time Result Fail <br /> # Material ���� � � <br /> STP Sump 1 SUP Containment Fiberglass 40" 39" Hydrostatic-Electronic 8:30 10" .00019 9:00 .003gph Pass <br /> STP Sump 2 REG Containment Fiberglass 40" 39" Hydrostatic-Electronic 8:30 10" .00050 9:00 008gph Pass <br /> STP Sump 3 DSL Containment Fiberglass 40" 39" Hydrostatic-Electronic 9:02 10" 00050 9:32 .008gph Pass <br /> Dispenser Pan 1/2 Bravo Metal 32" 8" Hydrostatic-Electronic 9:19 2" .00042 9:34 .010gph <br /> Pass <br /> Dispenser Pan 3/4 Bravo HDPE 32" 8" Hydrostatic-Electronic 9:03 2" .00086 9:18 1 .020gph Pass <br /> Comments: <br />