Laserfiche WebLink
Ameron Dualoy° Pipe Monitoring System <br /> Table 2. Temperature Effect Data for Ameron Dualoy° Pipe* <br /> Evacuation Fill Without Vapor With 300 ml Vapor With Gr vity Fill <br /> Parameter Cold Hot Combined Cold Hot Combined Hot 1 Hot 2 <br /> Low Level in 7.44 7.53 7.44 7.56 7.78 7.56 10.375 10.188 <br /> High Level in 7.69 7.81 7.81 7.94 8.25 8.25 10.75 10.375 <br /> dL in 0.25 0.28 0.37 0.38 0.47 0.69 0.38 0.19 <br /> Low Tem de F 36.6 62.9 36.6 39.3 65.6 39.3 76.1 78.9 <br /> High Tem de F 70.7 99.7 99.7 70.1 97.3 96.6 100.4 96.9 <br /> T de F 34.1 36.8 63.1 30.8 31.7 57.3 24.3 18 <br /> L/dT in/de F 0.0073 0.0076 0.0059 0.0123 0.0148 0.0120 0.0154 0.0104 <br /> Average in/de F 0.0075 0.0136 0.0129 <br /> orst Case in/de F 0.0076 0.0148 <br /> Extra olate to 300 ft** 3.26 6.35 7.255 <br /> * Table 2 contains all of the data for the temperature effects. "Without Vapor" data was obtained using the interstitial evacuation <br /> process for filling the interstice. "With 300 ml Vapor" was obtained by adding 300ml of air to the interstice prior to the tests. "Gravity <br /> Fill" was obtained from filling the interstice using gravity. An unknown amount of trapped air was likely present in the connectors of <br /> the pipe. <br /> ** Line length 300 ft, with a temperature change of 30 deg F. <br /> Page 9 of 12 <br />