0 <br /> N <br /> F <br /> U' <br /> Q' <br /> 0- <br /> 0 <br /> U GENERAL NOTESELECTRICAL SYMBOLS NEW PANEL BOARD A SURFACE MOUNTED 65/22 K.A.I.C. SERIES RATED NEW PANEL BOARD B SURFACE MOUNTED 65/22 K.A.I.C. SERIES RATED <br /> SYMBOL DESCRIPTION 120/208 VOLTS 3 PHASE 4 WIRE 100 AMP. BUS 120/208 VOLTS 3 PHASE 4 WIRE 400 AMP. BUS <br /> 1. THE ELECTRICAL WORK SHALL INCLUDE FURNISHING ALL LABOR, SUPERVISION, MATERIALS, EQUIPMENT, <br /> TOOLS, TRANSPORTATION, INSURANCE AND PERFORM OPERATIONS REQUIRED TO CONSTRUCT AND INSTALL CIRCUIT BREAKER TYPE 100 MCB FED FROM wIREWAY CIRCUIT BREAKER TYPE 300 MCB FED FROM wIREWAY <br /> LOAD- V. A. LOAD- V. A. <br /> COMPLETE AND OPERATIVE ELECTRICAL SYSTEM IN ACCORDANCE WITH THE SPECIFICATIONS AND CKT.T TRIP LOAD SERVED LOAD SERVED NO. TRAP CK NO.AMIP NO LOAD SERVED LOAD SERVED NO.TRIP CK <br /> DRAWINGS. PROVIDE FURNISH AND INSTALL COMPLETE AND READY FOR OPERATION AO B0 CO AO B0 CO <br /> 1 20 1 GENERAL LTG 484 SPARE 1 20 2 1 50 2 ESPRESSO E01 2028 WATER HEATER Eo3 2 30 2 <br /> ° 2. ALL MATERIAL FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE LATEST ACTIVE OR CONDUIT UP +2" UNLESS NOTED 3 20 1 540 4000 <br /> ADOPTED EDITIONS OF THE CALIFORNIA ELECTRIC CODE, STATE OR LOCAL ELECTRICAL CODES, AND THE SHOW WINDOW REC. __ SPARE 1 20 4 3 2028 4 <br /> N CONDUIT DOWN 5 20 1 MENU BOARDS iso SPARE 1 20 6 5 50 2 ESPRESSO Eo1 4000 WATER HEATER Eo3 2 30 6 <br /> REQUIREMENTS OF THE UTILITY COMPANIES. WHERE CONFLICTS OCCUR, THE MORE STRINGENT OR THE -- O 2028 O <br /> r CODE ENFORCED BY THE AUTHORITY HAVING JURISDICTION SHALL APPLY. CONDUIT BELOW FLOOR 7 20 1 EXTERIOR LTG $40 SPARE 1 20 8 7 2028 8 <br /> Q 3. WORK INTENDED, BUT HAVING MINOR DETAILS OBVIOUSLY OMITTED OR NOT SHOWN SHALL BE 9 20 1 BUILDING SIGNAGE 1200 SPARE 1 20 10 9 50 2 ESPRESSO E01 1800 BLENDER E08 1 20 10JASON D <br /> FURNISHED AND INSTALLED COMPLETE TO PERFORM REQUIRED FUNCTION. CONDUIT IN CEILING OR WALL 2 #12 THWN-CU 11 20 1 BUILDING SIGNAGE 1200 SPARE 1 20 12 11 4000 Eos 1 20 12 <br /> lsoo BLENDER � <br /> 4. ELECTRICAL PLANS ARE DIAGRAMMATICAL. DO NOT SCALE. COORDINATE ACTUAL LOCATIONS OF ALL 3 #12 THWN-CU IN 1/2" CONDUIT (2 CIR. & 1 NEUTRAL WIRES) 13 20 1 LIGHTING CONTROLS 1200 SPARE 1 20 14 13 50 2 GRINDERS4000 <br /> E01 1800 BLENDER E08 1 20 14 <br /> ° DEVICES AND ROUTING OF ALL RACEWAYS WITH ARCHITECT AND ALL TRADES PRIOR TO ANY ROUGH-IN. � 4 #12 THWN-CU IN 3/4" CONDUIT (3 CIR. & 1 NEUTRAL WIRES) 15 20 1 SPARE -- SPARE 1 20 16 15 1440 BEV DISPENSER Eos 3 20 16 <br /> 17 20 1 SPARE -- SPARE 1 20 18 17 20 1 GRINDERS Z�650 <br /> 1GNIC <br /> 440 18 <br /> ° 5. ALL MATERIALS SHALL BE NEW AND IN GOOD CONDITION. THE MATERIAL SHALL BE THE PRODUCT OFARCHITECT <br /> 0 SUBSTANTIALLY ESTABLISHED AND RECOGNIZED MANUFACTURER'S. SPLIT BUS 19 20 1 GRINDERS > 20 <br /> N /� HOME RUN 19 20 3 CONDENSOR E32 128° SPARE 1 20 20 21 20 1 GRINDERS E02 1440 BEV DISPENSER Eos 3 20 22 <br /> E 6. THIS CONTRACTOR SHALL COORDINATE HIS WORK SO THAT IT DOES NOT INTERFERE WITH THE WORK OF1260 650 <br /> 50 <br /> ALL OTHER TRADES. IT SHALL BE THIS CONTRACTOR'S RESPONSIBILITY TO SEE THAT THIS WORK IS Q JUNCTION BOX 21 SPARE 1 zo 22 23 20 1 GRINDERS E02 1440 24 <br /> 6; <br /> INSTALLED IN A TIMELY MANNER. PLAN AND INSTALL ALL ELECTRICAL WORK IN SUCH A MANNER AS TO E 23 1280 SPARE 1 20 24 25 20 1 GRINDERS E02 1440 26 9 SE 3RD AVE, SUITE 110 <br /> `a PREVENT OBSTRUCTIONS, AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. CONSULT ALL CONTRACT &R 20A, 1 P, 125V, GROUNDING TYPE DUPLEX RECEPTACLE, 25 20 2 EVAPORATOR l000 SPARE 1 20 26 27 20 1 GRINDERS E02 1440 > BEV DISPENSER Eos 3 20 28 PORTLAND, OR 97214 <br /> DRAWINGS FOR CONDITIONS AFFECTING THIS WORK AND VERIFY SPACES IN WHICH WORK WILL BE E = EXISTING; R = EXISTING RELOCATED l000 sso V. 503.552.9079 <br /> 27 SPARE 1 20 28 29 20 1 GRINDERS 9�1 <br /> 1440 30 <br /> INSTALLED. NOTIFY ENGINEER IMMEDIATELY OF POSSIBLE CONFLICTS. WHERE INTERFERENCE WITH SWITCH RATED DUPLEX RECEPTACLE. TIE STRAP REMOVED FOR "CONSTANT" -- F. 503.241.7055 <br /> STRUCTURAL, MECHANICAL OR OTHER FEATURES EXIST, OR WHERE JOB CONDITIONS REQUIRE AND SWITCHED LEG CONTROL WIRING. 29 20 1 SPARE -- SPARE 1 20 30 31 20 1 GRINDERS 440 32WWW.GNICHARCH.COM <br /> REASONABLE CHANGES IN LOCATIONS AND ARRANGEMENT OF INDICATED EQUIPMENT, CONDUIT, OUTLETS 20A, 1P, 125V, GFCI TYPE DUPLEX RECEPTACLE 31 20 1 SPARE Ir-- > SPARE 1 20 32 33 30 2 WATER HEATER Eo3 < 1328 > ICE MACHINE E10 1 20 34 <br /> _° <br /> ENGINEER.NIEERG. CONTRACTOR SHALL MAKE SUCH CHANGES WITHOUT EXTRA COST TO OWNER, ARCHITECT OR � SWITCH RATED DUPLEX RECEPTACLE. TIE STRAP REMOVED FOR "CONSTANT" 33 20 1 SPARE __ SPARE 1 20 34 35 sso WATER HEATER E3o 1 20 36 <br /> 3 AND SWITCHED LEG CONTROL WIRING. __ 2028 <br /> 35 20 1AE , SPARE __ SPARE 1 20 36 37 30 2 WATER HEATER E03 960 WATER HEATER E30 1 20 38 <br /> 0 7. THIS CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS AND VISIT THE SITE PRIOR TO SUBMITTING 20A, 1P, 125V, GROUNDING TYPE DOUBLE DUPLEX RECEPTACLE 37 40 3 3720 2028 <br /> RTU-1 __ SPARE 1 20 38 39 WATER SOFTENER E31 1 20 40 <br /> THEIR BID. HE SHALL INCLUDE ALL WORK IN THEIR BID DISCERNIBLE FROM REVIEW OF DOCUMENTS 1200 s] <br /> E AND SITE VISIT. NO SUBSEQUENT ALLOWANCES WILL BE MADE FOR LACK OF REASONABLE REVIEW OF 20A, 1 P, 125V, DEDICATED GROUNDING TYPE DOUBLE DUPLEX RECEPTACLE 39 3720 SPARE 1 20 40 41 20 1 SPARE 360 SECURITY SYSTEM 1 20 42 o r <br /> DOCUMENTS AND SITE VISIT. 41 3220 SPARE 1 20 42 43 20 1 SPARE 360 SOUND SYSTEM 1 20 20 E 17866 <br /> ° 8. THIS CONTRACTOR SHALL SUBMIT FOR APPROVAL EIGHT (8) SETS OF SHOP DRAWINGS ON THE 9504 77201 6540 1 45 20 1 SPARE -- > SPARE 1 20 22 EXP.61301 Z <br /> FOLLOWING: PANELBOARDS, DISCONNECT SWITCHES, LIGHTING FIXTURES, LAMPS, DEVICES AND 47 20 1 SPARE __ SPARE 1 20 24 ti <br /> COVERPLATES, FIRE ALARM EQUIPMENT AND ANY OTHER ITEMS REQUESTED BY THE ARCHITECT. ® CEILING MOUNTED DUPLEX RECEPTACLE. LOAD DESCRIPTION DEMAND FACTOR VOLT - AMPS 540 Sj _��C7P'�'H <br /> o D.F. CONNECTED DEMAND GFCI 49 20 1 KITCHEN REC. __ SPARE 1 20 26 <br /> LIGHTING 1.25 5824 7280 540 <br /> 16 9. THIS CONTRACTOR SHALL LEAVE EACH ENTIRE ELECTRICAL SYSTEM IN PROPER WORKING ORDER AND NO LOW VOLTAGE BELL RECEPTACLES C.E.C. -- __ GFCI 51 20 1 KITCHEN REC. __ SPARE 1 20 28 <br /> `s SHALL REPLACE ANY WORK OR MATERIAL PROVIDED BY HIM UNDER THIS CONTRACT WHICH DEVELOPS MOTORS C.E.C. -- -- 53 20 1 CONVENIENCE REC. 360 SPARE 1 20 30 <br /> DEFECTS WITHIN (1) YEAR OF FINAL ACCEPTANCE BY OWNER. ® EXHAUST FAN MISC. EQUIPMENT 1.00 -- -- 3so <br /> $ KITCHEN EQUIPMENT 0.65 -- -- 55 20 1 EXTERIOR REC. __ SPARE 1 20 32 <br /> LIGHT SWITCH HVA EQUIPMENT 1.00 1 8840 16940 180 <br /> 10.THIS CONTRACTOR SHALL PROVIDE, MAINTAIN AND REMOVE AFTER CONSTRUCTION IS COMPLETE AND - 1 22764 1 24220 57 20 1 RTU REC. __ SPARE 1 20 34 <br /> ADEQUATE TEMPORARY POWER AND LIGHTING SYSTEM. ID DIMMER SWITCH PANELBOARD LOAD = 24220 V.A. o PROVIDE LOCK-ON DEVICE 59 20 1 SPARE -- SPARE 1 20 36 <br /> FULL LOAD AMPS = 67.3 A. (E) = EXISTING 60 20 1 SPARE SPARE 1 20 38 <br /> 1 1 .PANELBOARDS SHALL BE OF THE SAME MANUFACTURER, (SQUARE 'D', CUTLER-HAMMER, GE OR MOTOR RATED SWITCH VOLTAGE AND PHASE RATED W/ THERMAL OVERLOAD -- <br /> `� ITE/SEIMENS). PROVIDE SCREW-ON ENGRAVED NAMEPLATES FOR ALL DISTRIBUTION EQUIPMENT. PROTECTION. NEMA 3F� WHEN LOCATED OUTSIDE. 61 20 1 SPARE SPARE 1 20 40 <br /> $OS OCCUPANCY SENSOR SWITCH: "d" DESIGNATES SWITCHED DEVICES 63 20 1 SPARE SPARE 1 20 42 <br /> 12.THIS CONTRACTOR SHALL PROVIDE NEW, TYPED, PANELBOARD DIRECTORIES FOR ALL NEW AND/OR CEILING OCCUPANCY SENSOR: "d" DESIGNATES SWITCHED DEVICES 30374 29556 25806 <br /> OS <br /> EXISTING PANELS WITHIN THE SCOPE OF THIS PROJECT. THE DIRECTORIES SHALL INDICATE THE LOAD d <br /> TYPE AND AREA SERVED. PROVIDE ALL FIELD VERIFICATION WORK AS NECESSARY. NO- (#T) TELEPHONE OUTLET ROUGH-N WITH 3/4"C. AND PULL WIRE TO ABOVE LOAD DESCRIPTION DEMAND FACTOR VOLT - AMPS <br /> ACCESSIBLE CEILING (#T = QUANTITY OF TELEPHONE OUTLETS) D.F. CONNECTED DEMAND <br /> ° 13.LIGHTING FIXTURES SHALL BE FURNISHED COMPLETE WITH LAMPS, HANGERS AND INCIDENTALS. FIXTURES LIGHTING 1.25 <br /> SHALL BE INDEPENDENTLY SUPPORTED FROM THE STRUCTURE ABOVE. ALL LIGHTING FIXTURES, LAMPS > (#D) DATA OUTLET ROUGH-N WITH 3/4"C. AND PULL WIRE TO ABOVE RECEPTACLES C.E.C. 2700 2700 <br /> ° AND LENSES SHALL BE THOROUGHLY CLEANED PRIOR TO FINAL ACCEPTANCE. ACCESSIBLE CEILING (#D = QUANTITY OF DATA OUTLETS) MOTORS C.E.C. <br /> c MISC. EQUIPMENT 1.00 27344 27344 <br /> ° 14.WIRING DEVICES SHALL BE SPECIFICATION GRADE WITH HIGH IMPACT NYLON COVERPLATES. COLOR OF P COMBINATION TELEPHONE/DATA OUTLET ROUGH-N WITH 3/4"C. AND PULL KITCHEN EQUIPMENT 0.65 55692 36200 <br /> DEVICES AND COVERPLATES AS DIRECTED BY THE ARCHITECT. ACCEPTABLE MANUFACTURER'S ARE WIRE TO ABOVE ACCESSIBLE CEILING HVAC EQUIPMENT 1.00ITOTAL- 85736 66244 <br /> -- -- <br /> a HUBBELL, P&S, GENERAL ELECTRIC AND COOPER INDUSTRIES. <br /> C TOTAL LOAD SUMMARY PANELBOARD LOAD = 66244 V.A. o PROVIDE LOCK-ON DEVICE <br /> (#C) COAXIAL OUTLET ROUGH-N WITH 3/4"C. AND PULL WIRE TO ABOVE FULL LOAD AMPS = 183.8 A. (E) = EXISTING <br /> 15.WIRE SHALL BE 'THHN' OR 'XHHW' COPPER, 90'C, 600 VOLTS, SOLID SIZE 10 AND SMALLER, ACCESSIBLE CEILING (#C = QUANTITY OF DATA OUTLETS) <br /> 0 STRANDED SIZE 8 AND LARGER. ALL FEEDERS AND BRANCH CIRCUITS SHALL HAVE A GREEN CODE SIZE LOAD DESCRIPTION DEMAND FACTOR VOLT - AMPS <br /> 0 UG11a INCANDESCENT FIXTURE. TYPE "G". CIRCUIT #11. SWITCH a. D.F. CONNECTED DEMAND <br /> EQUIPMENT GROUND. MINIMUM SIZE WIRE #12 AWG, UNLESS OTHERWISE NOTED. LIGHTING 1.25 5824 7280 <br /> LIGHTING FIXTURE. R = EXISTING RELOCATED RECEPTACLES C.E.C. 2700 2700 <br /> __ 16.ALL INTERIOR WIRING SHALL BE IN EMT WITH STEEL, SET SCREW FITTINGS. EMT SHALL BE USED IN ALL ®R MOTORS C.E.C. -- -- <br /> ° BLOCK (CMU) WALLS. TYPE MC (METAL-CLAD) CABLE MAY BE USED ON THIS PROJECT SUBJECT TOMISC. EQUIPMENT 1.00 27344 27344 <br /> ®NL LIGHTING FIXTURE WITH EMERGENCY BALLAST. NL = NIGHT LIGHT KITCHEN EQUIPMENT ss 55692 36200 O <br /> MEETING ALL OF THE FOLLOWING CONDITIONS: 1 HVAC EQUIPMENT 1.00 16940 16940 <br /> 2 A. THE LOCAL AUTHORITIES HAVING JURISDICTION MUST ALLOW THE USE OF MC CABLE. 1 LAMP STRIPLIGHT - 108500 90464 <br /> B. THE ARCHITECT AND OWNER MUST APPROVE OF THE USE OF MC CABLE. PANELBOARD LOAD = 90464 V.A. o PROVIDE LOCK-ON DEVICE <br /> y C. THE CABLE STRUCTURE AND INSTALLATION ARE IN ACCORDANCE WITH UL, CEC AND LOCAL CODE WALL MOUNTED EMERGENCY LIGHT. FULL LOAD AMPS = 251.1 A. (E) = EXISTING `^ <br /> REQUIREMENTS. (y) <br /> ° D. THE MC CABLE CONDUCTOR SIZE MEETS THE REQUIREMENTS OF THE CONSTRUCTION DRAWINGS E3 DISCONNECT SWITCH O N <br /> AND CEC. THE MINIMUM WIRE SIZE SHALL BE #12 AWG., THHN OR THWN. LV LOW VOLTAGE O <br /> E. THE MC CABLE MUST CONTAIN AN CEC SIZED GREEN GROUND CONDUCTOR FOR ALL CIRCUITS. <br /> L <br /> F. RECORD DRAWINGS (AS-BUILT DRAWINGS) SHALL REFLECT THE USE AND ROUTING LOCATIONS OF +12" AFF 12" ABOVE FINISHED FLOOR LINE OF AREA WHERE SHOWN Q <br /> - THE MC CABLE. <br /> N 17.THIS CONTRACTOR SHALL COORDINATE AND MAKE FINAL CONNECTIONS FOR MECHANICAL EQUIPMENT. 0, 30 UNFUSED SAFETY SWITCH (AMPS) ^ ' ILL <br /> SIZE ALL FUSES/CIRCUIT BREAKERS PROTECTING MECHANICAL EQUIPMENT PER EQUIPMENT30/20 FUSED SAFETY SWITCH (AMPS SW/FUSE) (4)500-KCMIL, (1)#3G. ` V <br /> IN 4 <br /> MANUFACTURERS RECOMMENDATIONS. .O <br /> " CONDUIT. <br /> ° ® POWER PANEL N <br /> 18.THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL ELECTRICAL WIRING, RACEWAYS, OUTLET AND ZLO <br /> JUNCTION BOXES, MOTOR STARTERS, DISCONNECT AND CONTROLS FOR EQUIPMENT FURNISHED UNDER ® VIDEO/DATA TERMINAL PORT PROVIDED BY MILLWORK VENDORS I U Off. <br /> OTHER SECTIONS, UNLESS NOTED OTHERWISE. VERIFY EQUIPMENT REQUIREMENTS WITH EQUIPMENT <br /> MANUFACTURER PRIOR TO BID. (4)#3-CU, (1)#8G. (4)350, (1)#4G. O N J <br /> IN 1-1/4" CONDUIT. IN 3" CONDUIT. E CD Q � <br /> 19.THIS CONTRACTOR SHALL NOT INTERRUPT OR REMOVE ANY EXISTING CIRCUITS OR EQUIPMENT UNLESS M 400 AMP `~ <br /> NOTED OTHERWISE ON PLANS. ANY DAMAGED OR DISRUPTED CIRCUITS OR EQUIPMENT SHALL BE 120/208V PANELV'A' PANELV'B' Q LO U 0 <br /> RESTORED TO LIKE NEW CONDITION AT NO ADDITIONAL COST TO OWNER, ARCHITECT OR ENGINEER. 3o, 4W 120/208V 120/208V U N O�, `" N <br /> C/T METER/DISC. 30-4WIRE 30-4WIRE E Q <br /> 20.ALL PENETRATIONS OF FIRE-RESISTIVE FLOORS OR SHAFT WALLS SHALL BE PROTECTED BY MATERIALS r 1 0 <br /> 100 AMP 400 AMP V O E U � � N <br /> AND INSTALLATION THAT CONFORM TO UNDERWRITER'S LABORATORIES LISTINGS FOR 1100 AMP 300 AMP n 1 0 <br /> 'THROUGH-PENETRATION FIRE STOP SYSTEM.' THE CONTRACTOR SHALL SUBMIT TO THE ARCHITECT, =#1/0 GNDM.C.B. M.C.B. VJ m 0 0 <br /> SHOP DRAWING DETAILS, FURNISHED BY THE MANUFACTURER OF THE FIRE STOP MATERIAL, WHICH O D__ U) <br /> SHOW COMPLETE CONFORMANCE WITH THE UL. THE DRAWINGS SHALL BE SPECIFIC FOR EACH 0C) w __z co C/)PENETRATIONS, WITH ALL VARIABLES DEFINED. <br /> -1..- C>` m <br /> ^^L 5 O _p E O <br /> 21 .THE FINAL DETERMINATION OF EXIT LIGHTING LOCATIONS AND EGRESS PATHWAYS SHALL BE THE I..� C O o <br /> RESPONSIBILITY OF THE ARCHITECT. THE CONTRACTOR SHALL CONFIRM AND VERIFY THE LOCATIONS OF *NOTE - EX: DENOTES DEVICE IS EXISTING (4)500-KCMIL C/T CABINET & METER SOCKET <br /> IN4" CONDUIT. BY EC. EC TO ARRANGE <br /> ALL EXIT AND EMERGENCY LIGHTING WITH THE ARCHITECT PRIOR TO ANY INSTALLATION. FOR THE INSTALLATION OF C/TS & <br /> TO UTILITY XFMR METER BY UTILITY COMPANY <br /> 22.THE ELECTRICAL CONTRACTOR SHALL COORDINATE SYSTEM FURNITURE JUNCTION BOX LOCATIONS WITH BY <br /> EQUIPMENT <br /> LOCALY. BE APPROVED ISSUED FOR PERMIT: <br /> THE SUPPLIER AND MAKE ALL FINAL FLEXIBLE CONNECTIONS TO SAME. 09. 1 2, 1 8 <br /> GENERAL NOTES SHEET NOTE 1 POWER RISER DIAGRAM <br /> SCALE: NONE REV: DATE: DESCRIPTION: <br /> 1. THE CONTRACTOR SHALL SUBMIT A COMPLETE SET OF DRAWINGS TO A. PER CEC 408.4 - EVERY BRANCH CIRCUIT AND CIRCUIT MODIFICATION <br /> ELECTRICAL AND TELCO UTILITIES WITHIN ONE WEEK OF NOTICE TO PROCEED. MUST BE UNIQUELY IDENTIFIED. PROVIDE A TAG AT EACH CIRCUIT <br /> CONDUCTORS JUNCTION BOX, OUTLET, SWITCH, ETC. DESIGNATION WHICH <br /> 2. THE CONTRACTOR SHALL NOT TRENCH OR INSTALL CONDUITS (ON THE ELECTRICAL PANEL AND CIRCUIT NUMBER THE CONDUCTOR IS FED FROM. <br /> UTILITY OR LOAD SIDE) TO THE SES, THE UTILITY TRANSFORMER (PRIMARY <br /> OR SECONDARY), OR TO THE UTILITY CONNECTION POINT BEFORE RECEIVING <br /> A FINAL DESIGN FROM THE UTILITY. <br /> 3. THE CONTRACTOR SHALL NOT INSTALL EQUIPMENT PADS FOR THE SES OR SHEET NAME: <br /> ANY UTILITY EQUIPMENT (TRANSFORMERS, SWITCHING CABINETS, ETC) PRIOR <br /> TO RECIEPT OF FINAL PLANS FROM THE UTILITY COMPANY. <br /> 4. THE CONTRACTOR SHALL NOT BE COMPENSATED FOR ADDITIONAL WORK ELECTRICAL <br /> REQUIRED TO MEET THE REQUIREMENTS OF THE UTILITY WHICH IS THE <br /> RESULT OF PROCEEDING PRIOR TO RECEIPT OF FINAL DESIGN. COVER SHEET <br /> St.Louis-Montreal <br /> Rd'lficalcase SHEET NUMBER: <br /> engineering <br /> g g <br /> 796 Merus Court mechanical <br /> St.Louis,MO 63026 electrical E1 . 0 <br /> Oki T 636.349.11600 plumbing <br /> F 636.349.1730 fire protection <br /> oil aedificacase.coin structural <br /> COPYRIGHT 2018 <br />