C, <br /> FEB 27 2021 <br /> City of Stockton Police Department <br /> 22 East Market Street <br /> Stockton, CA 95202 <br /> Primary Tank <br /> Time Pressure AP <br /> 0 3.0 psi 0 <br /> 5 3.0 psi 0 <br /> 10 3.0 psi 0 <br /> 15 3.0 psi 0 <br /> 20 3.0 psi 0 <br /> 25 3.0 psi 0 <br /> 30 3.0 psi 0 <br /> 35 3.0 psi 0 <br /> 40 3.0 psi 0 <br /> 45 3.0 psi 0 <br /> 50 3.0 psi 0 <br /> 55 3.0 si 0 <br /> 60 3.0 psi 0 <br /> Industry Standards testing was performed on the Certified UL 2085 Con Vault <br /> 6,000 Gallon Gasoline tank and the internal (primary) tank was tested to 3.0 psi. <br /> The primary tank passed it's Industry Standards certification testing. No defects <br /> were observed and the Gasoline system was observed to be in compliance with <br /> Industrial Standards ConVaulttesfing requirements. <br /> Test Device:-Ashcroft T5500 SS 0-5 psi Pressure Gauge_ <br /> Test Gas:_Nitrogen Gas_ <br /> Test Pressure: 3.0 psi_ I '.. <br /> Test Duration: 60 minutes dank tna <br /> Tank Capacity: 6, 000 Gallons_ o� a bye <br /> Certified Tester: —Gary Reeves <br /> _ <br /> 21 <br /> REAII #30349 <br /> S �«a,sti oa <br /> ICC #8019664 Pool ca,fo 4 <br /> SP001 Level II #11111 <br /> NDT-UT Level III #001 <br /> Certified Environmental Professional <br />