Compliance Standard <br /> Design Construction of tank:_Double Wail AST UL 2085_ Yes ❑ No <br /> (CFC 21.5.4.1.1) <br /> Design of Supports: _Concrete & Steel_ X❑ Yes ❑ No <br /> (NFPA 30)(CFC 3404.2.7.7) <br /> Electrical wiring of fuel pump:_UL Approved_ ® Yes [-] No <br /> (CFC 3403.1) <br /> Piping System Components: _Steel_ X❑ Yes ❑ No <br /> (CFC 3403.6.2) <br /> Tank Normal venting: _2" 18'_Abovegrade_ XD Yes ❑ No <br /> (CFC 3404.2.7.3) <br /> Emergency Venting system: _Emergency vents_ X❑ Yes ❑ No <br /> (CFC 3404.2.7.4) <br /> Tank Labelling: _NFPA 704_ [x] Yes ❑ No <br /> (CFC 3404.2.3.1 - 3404.2.3.4) <br /> Overfill protection: _Over fill by driver observation_ X❑ Yes ❑ No <br /> (CFC 3404.2.9.6) <br /> Liquid Transfer of fluids: _Positive Displacement- [-X] Yes ❑ No <br /> (CFC 3405.2) <br /> Spill Control: _Concrete Pad & UL 2085 tank_ ❑X Yes ❑ No <br /> (CFC 3405.2) <br /> Protection from Vehicles: _Concrete wall_ X❑ Yes ❑ No <br /> (CFC 5704.2.9.7.4 & 5704.9.3 <br /> Grounding & Bonding of Electrical system:_Wire_ XYes F-] No <br /> (NFPA 77 - 3.1.2 & 29 CFR 1910.106(e)(6)(ii) <br /> Tank Anchorage: 4 Anchors_ ®Yes ❑ No <br /> (CFC 5704.2.8.5) <br /> Tank is suitable for continued use Yes_ ® Yes ❑ No <br /> (SPo0110) <br /> Gary Reeves <br /> SP001 Level//#11111 k <br /> Ree <br /> I ti`.rj(loll I�k <br /> Gary Reeves, LLC a <br /> 4649 Monarch Court <br /> Turlock, CA 95382 <br /> gary@garyreevesllc.org <br /> 209 661 6611 <br />