Laserfiche WebLink
Visual Inspection findings: A visual inspection of the tank and its affiliated <br /> pumps, piping and ancillary equipment did not reveal signs of leaks, corrosion, <br /> weld cracks or breaks, or scrapes in protective coating which may cause a <br /> release from the tank system. A description of all discrepancies noted during the <br /> [visual inspection is included with this report. Initials: icB <br /> Seismic/Anchoring: <br /> Civil engineer wet stamped seismic/dynamic/hydrostatic load calculations <br /> provided as Attachment"D" <br /> Seismic/Anchoring findings: The tank as designed and operated, and the <br /> containment area in which it is located are adequately anchored and are <br /> seismically sound. Initials: K c3 <br /> Leak Test: 191(g)(9)/192(k)(10) <br /> The waste oil storage tank and ancillary equipment were sealed <br /> and subjected to a positive air pressure of 1.0 psig. The system <br /> maintained this pressure for 10 minutes with no observable <br /> pressure drop. <br /> Integrity testing findings: Based on the above noted integrity test and the <br /> results obtained from that test, the tank has sufficient integrity for its intended <br /> use. Initials: /<<3 <br /> Tank Drawing: 191(g)(2)(E)/l 92(k)(2)(E)) <br /> Tank and fittings: See Appendix "B" <br /> Tank Dimensions (primary storage): <br /> 3'-9" wide x 3'-9"deep x 4'-11" tall <br /> Tank Height: <br /> Overall Height: 5'-3 1/2" <br /> Lodi Honda 5 <br />