Laserfiche WebLink
,Lip Tanknology <br /> Executive Summary <br /> Tracy Manufacturing Plant TRACY MFG PLANT <br /> 10100 W.Linne Road <br /> Tracy, CA 95377 <br /> • Tank Diesel:Are the Tanks Grounded And/Or Bonded Properly?- Ground tanks per NFPA 780 or other accepted <br /> industry standard. <br /> • Tank Diesel:Emergency Contact Numbers Posted As Required? -Emergency plan is required and should include <br /> posting of emergency contact numbers. <br /> • Tank Diesel:Emergency Vent Manufacturer-Primary Tank- There are no emergency vents on this tank, <br /> recommend using manway for emergency vent. <br /> • Tank Diesel:Filling Procedures Posted At Fill As Required? -Install signage at the fill point to document filling <br /> procedures. <br /> • Tank Diesel:Fire Valve Installed? -Install a fire valve on product transfer piping through which liquid could flow <br /> through gravity. <br /> • Tank Diesel:NFPA Signage-Install a sign or marking that meets the requirements of NFPA 704. <br /> • Tank Diesel:No Smoking Signage Present As Required? - Install"No Smoking No Open Flames" signage. <br /> • Tank Diesel:Stairways-Handrails-Platforms-Ladders-Visually spotted some paint failure and corrosion, <br /> Recommend cleaning and painting. <br /> • Tank Diesel: Tank Capacity And Tank ID Posted On The Tank As Required?- Clearly label tank with capacity and <br /> ID.Only Capacity Label is missing. <br /> • Tank Diesel: Tank Primary Level Gauge Type-Recommend installing liquid level gauge to monitor product level at <br /> all times. <br /> • Tank Diesel: Tank Support Condition - Supports have paint failure and corrosion,Recommend cleaning and <br /> painting. <br /> Estimated Repair Total,if applicable: <br />