Laserfiche WebLink
Tri-Regional Recommendations Page 1 I of 1-4 <br /> Appendix A <br /> TALE #2 RECOMMENDED MINIMUM VERIFICATION ANALYSES <br /> FOR UNDERGROUND STORAGE TANK INVESTIGA11ONS <br /> See explanation on following page.) <br /> Gasoline by7DiieselBTEX by VOCs b Semi-VOCs Oil& Grease PCBs b Total Lead b Title 22 Met- <br /> Tank Contents (Car- Y Y8015M or8021 B orbon Range) 82600 8260B by 8270C �z� by 1664A 8082 7421 als <br /> 82606 <br /> 1 <br /> Unknown Fuel C4-C36 X X X ' X <br /> Gasoline C4-C20 X ` X X <br /> Diesel C10-036 X X X <br /> Jet Fuel/Kerosene C9-C20 X X <br /> Heating Oil 010-C32 X X <br /> Stoddard Solvent(C8-C20) X <br /> Non-Chlorinated X <br /> hlorinated Solvents X X <br /> aste Oil or Unknown Contents X X X X X X X <br /> Notes: <br /> 1. EPA Method 8260B analyses must include all analytes listed in the method plus fuel oxygenates methyl-tertiary-butyl ether(MTBE), diisopropyl ^, <br /> ether(DIPE), ethyl-tertiary-butyl ether(EtBE),tertiary-amyl-methyl ether(TAME),tertiary-butanol (TBA), methanol and ethanol and fuel additives <br /> 1,2-dichloroethane(1,2-DCA) and ethylene dibromide (EDB or 1,2-dibromoethane). <br /> 2. If pentachlorophenol (PCP) is identified, analyze the soil and/or water sample for dioxins and furans by EPA Method 8290 and pesticides <br /> by EPA Method 8081 A. <br /> 3. Method 6010B may be used for all but the following metals, for which individual AA methods are required: Antimony&Arsenic by 7062, Cadmium <br /> by 7131A, Lead by 7421, Mercury by 74t1A, Nickel by 7521, Selenium by 7742, and Thallium by 7841. <br /> 4. Non-proprietary, performance based analytical methods may be used with approval of Regional Board staff <br />