Laserfiche WebLink
Test Protocol (cont.) <br /> 9. Inspection of the primary steel tank <br /> 'i. At this point the inspector should locate and note the leak detection port. <br /> ii. The integrity of the inner steel primary tank is accomplished by checking for fluid between the steel tank and the <br /> HDPE liner.See below. <br /> Cross Section of ConVault <br /> Air Void <br /> Interstice(between <br /> Primary and Secondary) <br /> Case:Steel tank is uncompromised - - <br /> Result:Fuel remains safely stored in tank <br /> The inspector should obtain a clean wood orplastic inspection(non-pointed)rod ofsufficientlength to reach the full depth <br /> of the innersteel tank.With the inspection port cap opened,inserrthe rod to the bottom of the tube. <br /> iii. Withdraw the inspection rod and visually examine it. <br /> a. If the rod is dry and there is no liquid present then the primary steel tank is not leaking and the ConVault <br /> is suitable for continued use. <br /> See next page if the rod is wet. <br />