Summary <br /> As an owner of a ConVault you are NOT required to employ Certified Inspectors or a registered Professional Engineer to <br /> perform inspections on ConVault ASTs up to 5,000 gallons for most installations. <br /> For ConVault ASTs from 5,001 to 12,000 gallons you will need an External Inspection by a Certified Inspector once every <br /> 20 years for most installations. <br /> Monthly and yearly inspections by the tank owner or a designated employee are required by SP001,and Inspection <br /> Checklists are provided in Appendix C of the document. <br /> ConVault requires that the interstice be checked on a weekly basis using the inspection port and rod method <br /> described on Page 4. <br /> A newly installed ConVault AST will meet all the requirements of the SP001 checklists. <br /> Visit: www.epa.gov/emergencies/docs/oil/spcc/integrity-testing-factsheet.pdf <br /> if you have any questions regarding the EPA Spill Prevention,Control and Countermeasure Plan(SPCC)Program <br /> t , <br /> f <br />