Laserfiche WebLink
Food Express, Inc. <br /> Certified UL 142 - 500 Gallon Used Oil Tank <br /> Bottom 1 foot 2 foot 3 foot <br /> 0.205 0.206 0.208 0.209 <br /> 0.200 0.209 0.210 0.208 south <br /> 0.198 0.211 0.211 0.211 <br /> 0.200 0.210 0.212 0.210 <br /> 0.199 0.208 0.210 0.209 west CoMed UL 142 _ S <br /> 5w eavan <br /> 0.198 0.209 0.207 0.211 Und 0909 h <br /> 0.197 0.211 0.210 0.210 TW* o <br /> 0.198 0,210 0.212 0.208 north p <br /> 0.200 0.209 0.211 0.210 <br /> 0.200 0.208 0.209 0.211 <br /> 0.199 0.209 0.211 0.209 east <br /> 0.200 0.207 0.209 1 0.207 <br /> 3 foot <br /> 2 foot <br /> 1 foot <br /> bottom <br /> Non destructive metal thickness testing was performed utilizing a Certified Danabmic EHC- <br /> 09DL-CW Digital Ultrasound thickness gauge. Calibration of the certified non destructive <br /> gauge was performed on May 17, 2017, and prior to conducting the certified testing of the <br /> 270 Gallon Motor Oil tank. Non destructive testing consisted of A point measurements in <br /> every square foot throughout the lower half of the tank. The average measurements are <br /> reported in the boxes and no metal defects were observed. The 500 Gallon Use Oil Tank <br /> passed its certification testing and is certified for continues in-service use. System is <br /> classified as a Category III system. Biannual testing is required. <br /> Gary Reeves <br /> nk lha.,! <br /> y~ � <br /> �yp,11111 <br /> Steel Tank Institute EW!;/&W <br /> Level II SP001 #11111 <br /> NDT-UT Level III#001 &11 a <br /> ASNT-TG1A#073128 May 17, 2017 S,o�ai Ce�f�e <br />