Laserfiche WebLink
Monitoring System Certification <br /> D. Results of Testing/Servicing <br /> Software Version Installed: 0.75 <br /> Complete the foliowin checklist: <br /> 0 Yes ❑ No* Is the audible alarm operational? <br /> 19 Yes ❑ No* Is the visual alarm operational? <br /> ED Yes 0 No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> 0 Yes 171 No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> F-1 Yes E] No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) <br /> Z N/A operational? <br /> 0 Yes F1 No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> E3 N/A monitoring system detects a leak, fails to operate,or is electrically disconnected? If yes: which sensors initiate <br /> positive shut-down? (Check all that apply) 0 Sump/Trench Sensors; El Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? 9 Yes; [I No. <br /> E] Yes 0 No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no <br /> 0 N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> FLAPftp-5 fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 90% <br /> 0 Yes* 0 No Was any monitoring equipment replaced? If yes, identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> 0 Yes* 0 No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> 0 Product; 0 Water. If yes,describe causes in Section E,below. <br /> Yes El No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> Yes 0 No* Is all monitoring equivinent Merational ver manufacturer's gpecifications? <br /> In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: Mechanical leak detector on Diesel was replaced&still not passing 3gph @ 10 psi test. Placed Diesel <br /> out of service until further repairs & troubleshooting. Also,found annulars ace sensor® split to <br /> (91 & diesel) raised up-8" &water was found inthe annular space-2" of water. Removed water Fro—m <br /> annulars ace & corrected teen of the sensor& placed sensor at bottom of tank. <br /> Page 2 of 4 <br /> UN-036-2/4 www.unidoes.org Rev.01/17/08 <br />