Laserfiche WebLink
BULLETIN October 17, 2011 • TB0811-03 <br /> DC400 Dispensing Cutoff System <br /> Product Revision Differences iD <br /> The table below highlights differences between the legacy DC400 system and the current system. <br /> Legacy Release Current Release <br /> Geometric Form Factor Rectangular Circular <br /> Picture of the 404-4 <br /> xv <br /> Controller ® � <br /> Installation Instructions, 000-0312 000-0316 <br /> document part number <br /> Power Wiring 7 wires: 6 wires: <br /> •Black (line voltage) •Black(line voltage) <br /> •Blue (Neutral) •White (Neutral) <br /> •Green (Ground) •Green (Ground) <br /> •Orange (Line Voltage, Relay Out) •Orange(Line Voltage, Relay Out) <br /> •Orange/Black(Line Voltage, Relay in) -Orange/Black(Line Voltage, Relay in) <br /> • Red (Line Voltage) • Green (Safety Ground) <br /> •Yellow(Neutral) <br /> Power Conduit 1/2" Conduit 3/4" Conduit with mandatory EYS fitting <br /> Sensor Connectors and 4-Pin, 3-wire friction coupling 2-wire QuikOn connector to: <br /> Sensors connecting to either: •ULS, Non-Latching, Float Sensor(S404). <br /> •Latching Float Sensor(S404) <br /> •Non-Latching Optical Sensor(S406) <br /> Sensor Test Procedure •S404: Invert sensor and use supplied •S404: Invert sensor <br /> tool to reset it. <br /> •S406: Submerge and obscure light <br /> source. <br /> Installer and Service • Requires certification currently •Requires NEW certification obtained via <br /> Technician Certification obtained via Franklin Fueling Franklin Fueling Systems'TECHLAB <br /> Systems'TECHLAB portal: portal: http://techlab.franklinfueling.com <br /> http://techlab.franklinfueling.com <br />