Laserfiche WebLink
, <br /> 0 0 RE � <br /> SWRCB January Janua 2002 Q <br /> I VE[) <br /> AUG 06 <br /> 4. TANK ANNULAR TESTING 15 <br /> Test Method Developed By: X Tank Manufacturer _ Industry Standard 7 Profe ENTAL <br /> ij <br /> Other(Spec) ! r1 A <br /> Test Method Used: ❑Pressure X Vacuum 11 Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution:- '/2"x-30Hg. <br /> EMEMMITank# 1 Tank#2&3 Tank# Tank# <br /> Is Tank Exempt From Testing?' No No <br /> Tank Capacity: 12K 12K Split 6K/6K <br /> Tank Material: Glass Steel II Glass Steel II <br /> Tank Manufacturer: Modern Welding Modern Welding <br /> Product Stored: Regular 87 Super 91/Diesel <br /> Wait time between applying 30 Minutes 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 10:40 10:25 <br /> Initial Reading(RI): -10 Hg. -10 Hg. <br /> Test End Time: 11:40 11:25 <br /> Final Reading(RF): -10 Hg. -10 Hg. <br /> Test Duration: 1 Hour I Hour <br /> Change in Reading(RF-Rj): 0 Hg. 0 Hg. <br /> Pass/Fail Threshold or Criteria: No Loss in Hg. No Loss in Hg. <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and Yes Yes <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)1 <br />