Laserfiche WebLink
EMERGENCY PUMP AND DISPENSER SHUT OFF CHECKLIST Q <br /> FACILITY>y % DATE <br /> ADDRESS <br /> 1. Authorize one dispenser of each product at the ARCOmatic. Go to dispenser of authorized <br /> product and turn on the handle. , <br /> 2. Turn emergency switch, independent of ARCOmatic switch, to stop position. Note: each <br /> emergency stop switch must be tested independently. <br /> 3A. Tokheim Dispensers Only <br /> Check relays in (I)-power centers and (2) turbine relay boxes to verify that they are open and <br /> that power to the turbines is off. <br /> Open turbine sumps and verify turbines are off. Note results below. <br /> 3B. Gilbarco&Wayne Dispensers Only <br /> Verify at least one dispenser of each product will shut off. Check turbine relay boxes to verify <br /> that they are open and that power to the turbines is off. <br /> Open turbine sumps and verify turbines are off. Note results below. <br /> 4. ARCOmatic Sites Only:--1TVCR's do not have emergency stop switches on console.) <br /> Authorize one dispenser to verify that dispenser power shuts down and/or turbine power shuts <br /> down. Repeat procedure#4 for each dispenser and note results below. <br /> STOP SWITCH SHUTS DOWN COMMENT/REPAIRS <br /> TURBINE DISPENSER <br /> (YIN) (Y/N) <br /> ARCOmatic <br /> OUTSIDE WALL <br /> INSIDE STORE �/ y /�►�t9�'f',!/` �I�ii,� �i� <br /> OTHER <br /> S. Turn emergency switch back to run position. <br /> 6. Put station back in operation. <br /> 7. Install turbine circuit breaker and emergency stop decals supplied by ARCO if necessary. <br /> CONTRACTOR ,S�-0 711 C O�j�/'Gr..'/ SIGNATURE <br /> Comments: <br />