Laserfiche WebLink
Idarns <br /> recision <br /> nstrumentation, Co. <br /> 3031 TISH WAY,SUfTE 200-SAN JOSE,CALIFORNIA 95128 <br /> (408) 244-6739- FAX(408)244-6801 <br /> ARCO Products Company <br /> API/Ronan X76S Leak Detection Certification <br /> Facility # �Do7� Date <br /> Address <br /> I Verify Intrinsic Safety <br /> Proper field wire termination <br /> Proper power wiring with earth ground and individual breaker <br /> Complete isolation of I.S. field wiring from any other wiring <br /> especially in gutters <br /> Proper use of E.Y.S. fitting/ <br /> II. Check for proper panel installat on <br /> Panel mounted in a nonhazarAo s to /In <br /> Panel is accesible to station ope a 'o�s <br /> All field wiring is tabellel t na strip or adjacent gutter <br /> All wiring to panel is Brough r u h a propriate punch-outs <br /> III Check for proper probe installation <br /> Piping sump sensors suspended within one inch of sump bottom <br /> Double walled FRP tank sensors(LS-7) installed at bottom of tank <br /> with a pull wire circumventing the primary tank and accessible <br /> from grade. <br /> Annular space risers should be sealed watertight with field <br /> wiring penetrating using cable grips or other apprpriate method <br /> Probe leads terminating in a watertight J-box <br /> IV Check system operation <br /> Verify proper fuctioning of alarm horn and lights by pushing <br /> the test button <br />