Laserfiche WebLink
' TABLE 1 <br /> GROUNDWATER TREATMENT SYSTEM FLOW DATA <br /> Speedy Foods <br /> 8200 N Hwy 99, Stockton, California <br />' (Page I of 2) <br /> Meter Period Measured Period <br />' Date Reading Flow Flow Rate Flow Rate Comments <br /> (gallons) (gallons) (gpm) (mgd) <br />' 11/05/03 0 0 1 9 0 System Startup <br /> 11/05/03 620 620 20 2 7 E-3 INF, C1, EFF samples collected <br /> 11/06/03 2487 1867 1 7 1 9 E-3 <br /> 11/07/03 2620 133 0 1 3 E-4 System down due to switch malfunction <br />' 11/10/03 4220 1600 1 5 5 3 E-4 INF, C1, EFF samples collected <br /> 11/11/03 6602 2382 1 5 2 4 E-3 <br /> 11/12/03 8315 1713 14 1 7 E-3 <br />' <br /> 11/13/03 9510 1195 1 7 1 2 E-3 <br /> 11/14/03 12111 2601 1 8 2 6 E-3 <br /> 11/17/03 18445 6334 1 5 2 1 E-3 INF,C1 EFF samples collected <br />' 11/18/03 21685 3240 1 3 3 2 E-3 System shut down for carbon change <br /> 11/21/03 21685 0 0 0 Pump removed and skimmer installed in extraction well <br /> 12/01/03 21685 0 0 0 Carbon replaced <br /> 12/03/03 21685 0 0 0 Skimmer removed and pump replaced in extraction well <br />' 12/04/03 21685 0 0 0 Carbon wetted and system pressure tested (gaskets ordered) <br /> 12/10/03 21871 186 0 0 Gaskets changed and system pressure tested <br /> 12/11/03 22425 554 1 9 0 System re-started and samples collected from C1, C2 EFF <br /> 12/12/03 24947 2522 20 2 5 E-3 <br /> IrP 92/15/03 33090 8143 1 8 2 7 E-3 INF, C1 C2,EFF samples collected <br /> 12/16/03 35939 2849 1 65 2 8 E-3 <br />' 12/18/03 40246 4307 14 22 E-3 C1, C2 EFF samples collected, replaced water filter <br /> 12/22/03 49218 8972 14 2 2 E-3 INF, C1, C2, EFF samples collected <br /> 12/26/03 55955 6737 12 1 7 E-3 C1, C2, EFF samples collected <br />' 12/30/03 62250 6295 1 35 1 6 E-3 INF C1,C2, EFF samples collected, replaced water filter <br /> 01/02/04 69094 6844 1 3 2 3 E-3 C1 C2 EFF samples collected <br /> 01/05/04 73580 4486 1 2 1 5 E-3 INF,C1 C2,EFF samples collected, replaced filter adjusted flow to 1 8 gpm <br /> 01/09/04 82091 8511 1 4 21 E-3 C1, C2 EFF samples collected replaced filter adjusted flow to 1 6 gpm <br /> t01/15/04 95236 13145 20 22 E-3 C1, C2 EFF samples collected adjusted flow to 1 7 gpm <br /> 01/23/04 111470 16234 1 7 2 0 E-3 C1, C2, EFF samples collected <br /> 01/30/04 121240 9770 1 7 1 4 E-3 C1,C2, EFF samples collected <br />' 02/09/04 138652 17412 1 5 1 7 E-3 INF,C1,C2 EFF samples collected <br /> 02/17/09 153262 14610 1 7 1 8 E-3 C1, C2, EFF samples collected <br /> 02/23/04 163120 9858 1 55 1 6 E-3 Ci C2 EFF samples collected <br /> 03/01/04 176709 13589 1 5 1 9 E-3 C1,C2, EFF samples collected,Temp storage tank removed from system <br /> 03/08/04 190804 14095 1 5 1 9 E-3 INF,C1,C2, EFF samples collected <br /> 03/15/04 204110 13306 1 45 1 9 E-3 C1 C2 EFF samples collected <br /> 03/16/04 205798 1 1688 1 5 1 3 E-3 <br /> 03/24/04 219260 13462 1 4 1 7 E-3 C1,C2, EFF samples collected <br /> 03/30/04 225713 6453 1 5 1 1 E-3 C1,C2, EFF samples collected <br /> 04/05/04 234871 9158 1 4 1 5 E-3 C1, C2, EFF samples collected <br /> 04/12/04 238128 3257 1 4 47 E-4 System down, no samples collected <br /> 04/13/04 240066 1938 1 5 1 9 E-3 Reduced flow to approx 1 gpm <br /> 04/14/04 241086 1020 1 0 1 4 E-3 INF,C1 C2, EFF samples collected <br /> 04/26/04 254319 13233 1 0 1 1 E-3 System down restarted system then sampled C1,C2, EFF <br /> 05/03/04 263156 8837 09 1 3 E-3 System running,sampled Ci,C2, EFF <br />