Laserfiche WebLink
may also to be applied to the overall condition of the vessels and determination <br /> for continued suitability for usage, however, STI-SP001 is not the exclusive <br /> required method of testing for tanks at this facility. Testing methods which are <br /> in accordance with the US EPA requirements for testing are "any two of the <br /> methods listed above and highlighted in red, may be applied under certain <br /> conditions, and with the acceptance of the local CUPA. . <br /> Inspection methods as articulated in STI SP001 inspection and testing methods <br /> may also to be applied to the overall condition of the vessels and determination <br /> for continued suitability for usage, however, STI-SP001 may not be the only <br /> required method of testing for tank at this facility. Non-Destructive Testing <br /> methods which are in accordance with the US EPA requirements for testing are <br /> "any two of the methods" listed above and highlighted in red, may be substituted <br /> for pressure-vacuum testing for these tanks. The methods applied are both the <br /> ultrasonic testing for steel thickness and the inspection of the secondary <br /> containment both visually and via hydrocarbon sensor. <br /> 60 <br />