Laserfiche WebLink
2.0 Secondary <br /> lbservations Comments/Recommendations <br /> Secondary Containment Type Concrete wall/floor Not true secondary because the wall is just a curb 6" <br /> high. diesel tanks share this area. <br /> Secondary Containment Length 66' <br /> Secondary Containment Width 20' <br /> Secondary Containment Height 6" <br /> Secondary Containment Volume (gallons) 4937 gal <br /> Secondary Containment Condition None <br /> (breaches,foreign material, liquid) <br /> Secondary Containment Drain Valve es Open conduit w/plug <br /> Installed? <br /> Drain Valve Locked? No <br /> Sump Pump Installed? N/A <br /> Is The Sump Pump Float or Manually N/A <br /> Activated? <br /> Other <br /> Observations3.0 Secondary Containment(AST) <br /> Secondary Containment(AST)-D/W, Double <br /> Bottom or Secondary Containment(Pans, Double Wall Tank <br /> Boxes or Containers) <br /> ST Containment Condition? Dry? Good/Dry <br /> Drain Valve Installed No <br /> Drain Valve Locked? N/A <br /> Other <br /> 4.0 Tank Appurtenances <br /> Piping Observations Comments/Recommendations <br /> Ancillary Equipment: Piping/Piping Good/corrosion free <br /> Connections (leaks, corrosion, supports) <br /> Other <br /> ObservationsValves <br /> Anti Siphon Valve installed? Yes <br /> Anti Siphon Valve Manufacturer Unknown <br /> Anti Siphon Valve Model 150 swp/300wog <br /> Is the Anti Siphon Valve Operational And <br /> Properly Sized? es <br /> Fire Valve Installed? N/A <br /> Fire Valve Manufacturer N/A <br /> Fire Valve Model Number N/A <br /> Is the Fire Valve Operational? N/A <br /> Other <br /> ObservationsVents <br /> Normal Vent Manufacturer OPW <br /> Normal Vent Size 2" <br /> Normal Vent Model OPW/no23 <br /> Normal Vent Condition Good <br /> Normal Vent Properly Sized? Yes <br /> 4 <br />