My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2013 - 2018
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
Y
>
YOSEMITE
>
1711
>
2300 - Underground Storage Tank Program
>
PR0231455
>
COMPLIANCE INFO_2013 - 2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/6/2020 1:54:57 PM
Creation date
5/5/2020 4:53:14 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2013 - 2018
RECORD_ID
PR0231455
PE
2361
FACILITY_ID
FA0003612
FACILITY_NAME
Yosemite Avenue Arco AmPm
STREET_NUMBER
1711
Direction
E
STREET_NAME
YOSEMITE
STREET_TYPE
Ave
City
Manteca
Zip
95336
CURRENT_STATUS
01
SITE_LOCATION
1711 E Yosemite Ave
P_LOCATION
04
P_DISTRICT
005
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
459
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
f <br /> Arco Station #6020 1711 E.Yosemite Ave., Manteca SR0066934, revised <br /> e. Secondary piping soap test: One hour pressure test for all piping, per manufacturer's <br /> guidelines. If there are no manufacturer's guidelines, test shall be performed using <br /> an applicable method specified in an industry code or engineering standard. <br /> Completed 5/9/13 <br /> f. 24-hour hydrostatic test (or equivalent) on all UDC sumps. Completed 5/10/13 <br /> g. Verification of dispenser footprint contained by the UDCs. Completed 5/16/13 <br /> h. Visual inspection of piping within the dispensers. Completed 5/16/13 <br /> i. Witness soil sampling. Completed 5/2/13 <br /> j. Sensor functionality: Functionality of the monitoring system for the 87#1 and #2 <br /> annular sensors must be verified to ensure that monitoring has been restored to <br /> meet the requirements of Title 23 California Code of Regulations and the Health & <br /> Safety Code. Completed 6/24/13 <br /> 4. If concrete will be broken near the tank, a secondary containment test must be <br /> performed on the affected USTs once concrete is poured in accordance with the <br /> manufacturer's guidelines. <br /> 5. Secondary containment testing for the UDC sumps and piping is required six months <br /> after installation. Provide 48 hours notification to the EHD when this test is scheduled. <br /> 6. Qualified service technicians must possess or work under the direct and personal <br /> supervision of an individual physically present at the work site who possesses all of the <br /> following: <br /> a. One of several permissible valid, current contractor's licenses issued by the <br /> Contractors State License Board (may be issued to the installation company), or a <br /> Tank Tester's license issued to the individual by the State Water Board, and <br /> b. A valid, current California UST Service Technician certificate issued by the <br /> International Code Council (ICC), and <br /> c. A valid, current certificate of training from the manufacturer(s) of the component(s) <br /> being tested, repaired, or serviced. <br /> 7. Qualified installers must possess or work under the direct and personal supervision of an <br /> individual physically present at the work site who possesses all of the following: <br /> a. A valid, current contractor's license issued by the Contractors State License Board, <br /> and <br /> b. A valid, current certificate of training from the manufacturer(s) of the component(s) <br /> being installed, and <br /> c. A valid, current UST Installation/Retrofitting certificate issued by the International <br /> Code Council (ICC). <br /> 8. Update and submit a copy of the "UST Monitoring Plan" for EHD approval. An approved <br /> copy will be returned for on site records. <br /> 9. A "UST Certification of Installation/Modification"form shall be submitted by the owner or <br /> the owner's agent (CCR Section 2635(d)) before this upgrade is considered complete by <br /> EHD. <br /> 2 <br />
The URL can be used to link to this page
Your browser does not support the video tag.