Laserfiche WebLink
Doug Wilson <br /> From: Doug Wilson <br /> Sent: Wednesday, March 17, 1999 2:43 PM <br /> To: Bill Merchant (E-mail); PAUL FERREIRA (E-mail) <br /> Subject: APPROVAL FOR 1771 YOSEMITE AND 16 E HARDING, ENTRY AND INSPECTION <br /> THE ABOVE PLANS ARE APPROVED SUBJECT TO THE FOLLOWING: <br /> 1 MUST CALL 48 HRS IN ADVANCE <br /> 2 TANKS MUST NOT HAVE OVER 1% DEFECTION (4 POSITION MEASUREMENT) <br /> 3 ENGINEER MUST ENTER TANK TO MAKE INSPECTION <br /> 4 THE EHD CAN REJECT THE TANK FOR CAUSE <br /> 5 CITY FIRE PERMITS REQUIRED <br /> 6 INTEGRITY TEST REQUIRED UPON COMPLETION <br /> 7 CONFINED SPACE ENTRY PERMIT REQUIRED TO BE ON SITE. <br /> 8 MAP TO HOSPITAL MUST BE PART OF SAFETY PLAN. <br /> 9 NOTE A MONITORING WELL WILL BE REQUIRED IF TANK IS FOUND TO BE STRUCTURALLY SOUND AND <br /> IS TO REMAIN, (IF CONTAMINATION IS FOUND ANYWHERE ON SITE). <br /> 10 PIPING MAY BE REJECTED BY EHD IF OBVIOUSLY NOT STRUCTURALLY SOUND IE STEEL PIPE ETC. <br /> 11 MUST PROVIDE INFO ON LAB AND SAMPLER IN ADVANCE FOR APPROVAL.. <br /> 1 <br />