Laserfiche WebLink
Time In: <br /> Time Out: <br /> op4�!!N• San Joaquin County <br /> tii Environmental Health Department <br /> W. 1868 East Hazelton Avenue, Stockton, CA95205-6232 <br /> • .. ;P Telephone: (209) 468-3420 Fax: (209)464-0138 Web:www.sjgov.org/ehd <br /> Underground Storage Tank Program Service Request Inspection Report <br /> Name of Facility: ARCO 06080 Date: 11/16/2018 <br /> Address: 85 E LOUISE AVE, LATHROP 95330 <br /> Requestor: MERLIN BOWEN, GETTLER RYAN INC Telephone: (925) 551-7555 <br /> Program Element: 2308- UST RETROFIT Request#: SR0079638 <br /> Inspection Type: 298 - UST RETROFIT REPAIR INSPECTION <br /> Onsite Service Technician: Brian Gan ICC Service Tech/Installer Exp. Date: 02/07/2019 <br /> Manufacturer training: OPW, 11/23/18 <br /> OVERALL INSPECTION NOTES AND COMMENTS <br /> NOTES <br /> -Witnessed overfill prevention testing for mechanical flappers on all tanks. All flappers were set at 93%. <br /> 87 tank has two drop tubes. Both had the same measurements(upper tube length = 80"). <br /> 91 tank upper tube length is 77 1/8". <br /> Diesel upper tube length is 77 5/8". <br /> -Verified removal of ball floats. <br /> The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br /> Safety Code. If a reinspection is required,fees will be assessed at the current hourly rate. <br /> Received by: Name and Title: Brian Gan, Technician <br /> EH Specialist: STACY RIVERA Phone: (209)468-3440 <br /> FA0003635 SR0079638 SC298 11/16/2018 <br /> EHD 23-01 Rev.06/30/15 Page 1 of 1 Underground Storage Tank Program Service Request Inspection Report <br />