Laserfiche WebLink
Eo � <br /> HOW TO LOCATE THE POSITION OF THE <br /> 71 SO AT 95% TANK CAPACITY Measuring Stick <br /> The length of the upper tube and the placement of <br /> the 71 SO valve body determine the shut-off point. <br /> Following the standard instructions for the OPW <br /> 71 SO will provide for initial shutoff at 95%. In all <br /> cases, the upper tube length must be a minimum of ' <br /> 6-1/2" plus the length of the riser pipe. All length 1 S <br /> measurements are in inches. Riser Pipe <br /> INSTRUCTIONSwith Face (A) <br /> Seal Adaptor To Tank <br /> Top (ID.} {B} <br /> . <br /> 1.) Find tank capacity (in gallons)from tank To Tank <br /> calibration chart provided by tank manufacturer. Bottom <br /> Iaj 257 <br /> 2.) Calculate 95%of capacity. q 7 yy 60 <br /> 6-1/2" <br /> 3.) Locate the 95% volume numb r on the tank <br /> calibration chart. 1 OG r, °r <br /> 4.) Find the dipstick number(X)which corresponds Figure 1 <br /> to the 95% tank volume. And, find the dipstick <br /> number(Y)which corresponds to the S EXAMPLE <br /> 100%volume. /V(-b �'� /(9^ 1.)For an Owens-Corning Model G-3 Fiberglass® <br /> Tank Calibration Chart: <br /> 5.)Subtract the dipstick number(X)from the tank Tank Capacity- 10,000 gal., nominal 9,403 gal. <br /> diameter(Y)to find the upper tube�reference NOTE: Use actual capacity only <br /> number(Z). 2 <br /> (Y)- {X)= (Z) 3 y 2.)95%of actual tank capacity= 0.95 x <br /> 6.)Subtract 2"from(Z)to find the upper tube depth 9403 gal. =8933 gal. <br /> (C). / �y 1/ 3.)The closest number which is less than 8933 gal. <br /> (Z) -2"= C Is 8910 gal. Choosing the closest number less <br /> than 95% of actual capacity ensures that the <br /> 7.}Is C less than 6-i/2"? /Y initial shutoff will occur when the tank is no more <br /> than 95%full. <br /> NO Upper tube length is C plus the distance <br /> from the top of the Face Seal Adaptor 4.)The calibration chart reading of 8910 gal. <br /> installed on the riser pipe to the inside, top corresponds to a dipstick measurement of 82". <br /> lip of the storage (A). <br /> Upper Tube Length -C + A 5.) Dipstick number(X)= 82" <br /> U <br /> pp g - ( ) Tank diameter(Y)= 92" <br /> (Y)-(X) =(Z) (92 "-82" = 10") <br /> YES Upper tube length is 6-1/2" plus the riser (Z)= 10" <br /> pipe measurement (A). <br /> 7.) (Z)-2"= C (10" -2"= 8") <br /> Upper Tube Length=6-1/2"+ (A) C _ 81, <br /> NOTE: You must find the actual tank capacity 7.) Is 8" fess than 6-1/2"? <br /> number that correlates to the 6-1/2"+ (A)depth <br /> for the station records. This number may also NO Measure the distance from the top of the <br /> be used for the purposes of calibrating an FSA-400 Face Seal Adaptor installed on the <br /> electronic tank level system. riser pipe to the inside, top lip of the storage <br /> tank and obtain measurement(A). <br /> Q Registered T.M.-Owens Coming F berglass Corporation Upper tube length= C + (A) <br /> 64 <br />