Laserfiche WebLink
Z.(! <br /> HOW TO LOCATE THE POSITION OF THE <br /> 71 SO AT 95%TANK CAPACITY /Measuring Stick <br /> The length of the upper tube and the placement of <br /> the 71 SO valve body determine the shut-off point. <br /> Following the standard instructions for the OPW <br /> 71 SO will provide for initial shutoff at 95%. In all <br /> cases, the upper tube length must be a minimum of <br /> 6-1/2" plus the length of the riser pipe. All length <br /> measurements are in inches. Riser Pipe <br /> INSTRUCTIONSwith Face (A) <br /> Seal Adaptor To Tank <br /> )D <br /> (I. . (B) <br /> 1.)Find tank capacity(in gallons)from tank Top To Tank <br /> calibration chartprovided by tank manufacturer. Bottom <br /> !1, o? <br /> 2.)Calculate 95% of capacity. 11,ZW 3 <br /> 6-1/2" <br /> 3.)Locate the 95% volume number on the tank <br /> calibration chart. 16r— <br /> %l/ t <br /> 4.) Find the dipstick number(X)which corresponds Figure 1 <br /> to the 95% tank volume. And, find the dipstick <br /> number(Y)which correspo � to the / A EXAMPLE <br /> loo%volume. 11C�_ _ 106_s8 _ 1.) For an Owens-Corning Model G-3 Fiberglass® <br /> Tank Calibration Chart: <br /> 5.) Subtract the dipstick number(X)from the tank Tank Capacity- 10,000 gal., nominal 9,403 gal. <br /> diameter(Y)to find the upper tube reference NOTE: Use actual capacity only <br /> number(Z). /, <br /> (Y)- (X) = (Z) !3 2.)95% of actual tank capacity = 0.95 x <br /> 6.) Subtract 2"from (Z)to find the upper tube depth 9403 gal. = 8933 gal. <br /> (C) Z " 11 /I 3.)The closest number which is less than 8933 gal. <br /> /3 ( )-2 = C Is 8910 gal. Choosing the closest number less <br /> than 95% of actual capacity ensures that the <br /> 7.) Is C less than 6-112"? Nv initial shutoff will occur when the tank is no more <br /> NO Upper tube length is C plus the distance than 95% full. <br /> from the top of the Face Seal Adaptor 4.)The calibration chart reading of 8910 gal. <br /> installed on the riser pipe to the inside, top corresponds to a dipstick measurement of 82". <br /> lip of the storage (A). <br /> 5.) Dipstick number(X) =82" <br /> Upper Tube Length =C + (A) Tank diameter(Y) = 92" <br /> YES Upper tube length is 6-1/2" plus the riser (Y)-(X)= (Z} (92 "-82" = 10") <br /> (Z) = 10" <br /> pipe measurement (A). <br /> 7.) (Z)-2" =C (10"-2"= 8") <br /> Upper Tube Length = 6-1/2" + (A) C _8" <br /> NOTE: You must find the actual tank capacity 7.) Is 8" less than 6-1/2"? <br /> number that correlates to the 6-1/2" + (A)depth <br /> for the station records. This number may also NO Measure the distance from the top of the <br /> be used for the purposes of calibrating an FSA-400 Face Seal Adaptor installed on the <br /> electronic tank level system. riser pipe to the inside, top lip of the storage <br /> tank and obtain measurement(A). <br /> m Registered T.M.-Owens Coming Fiberglass Corporation Upper tube length = C + (A) <br /> 64 <br />