Laserfiche WebLink
2-0 ��- <br /> HOW TO LOCATE THE POSITION OF THE <br /> 71 SO AT 95%TANK CAPACITY Measuring Stick <br /> The length of the upper tube and the placement of - 1. <br /> the 71SO valve body determine the shut-off point. <br /> Following the standard instructions for the OPW <br /> 71 SO will provide for initial shutoff at 95%. In all - <br /> cases, the upper tube length must be a minimum of <br /> 6-1/2" plus the length of the riser pipe. All length i <br /> measurements are in inches. Riser Pipe <br /> INSTRUCTIONS with Face <br /> Seal Adaptor <br /> daplo To Tank <br /> Top(I.D.} (B) <br /> 1.) Find tank capacity(in gallons)from tank To Tank <br /> calibration chart provided by tank manufacturer. Bottom <br /> 2.)Calculate 95%of capacity. g 915.3. 5 - <br /> 6-1/2" <br /> 3.)Locate the 95% volume number on the tank <br /> calibration chart. <br /> 4.) Find the dipstick number(X)which corresponds Figure 1 <br /> to the 95% tank volume. And, find the dipstick <br /> number(Y)which corresponds to the 4 EXAMPLE <br /> 100%volume. �07_� ���Y1 1.) For an Owens-Corning Model G-3 Fiberglass® <br /> J Tank Calibration Chart: <br /> 5.) Subtract the dipstick number(X)from the tank Tank Capacity- 10,000 gal., nominal 9,403 gal. <br /> diameter(Y)to find the upper tube reference NOTE: Use actual capacity only <br /> number(Z). <br /> tYl- (X) = (Z)7 �i� �� v 2.) 95% of actual tank capacity= 0.95 x <br /> �g-�d7 Y /Z 9403 gal. =8933 gal. <br /> 6.)Subtract 2"f,um ( )to find the upper tube depth <br /> (C)• 3.)The closest number which is less than 8933 gal. <br /> (Z) -2"= C /O - Is 8910 gal. Choosing the closest number less <br /> than 95% of actual capacity ensures that the <br /> 7.) Is C less than 6-1/2"? -1 p initial shutoff will occur when the tank is no more <br /> than 95% full. <br /> NO Upper tube length is C plus the distance <br /> from the top of the Face Seal Adaptor 4.)The calibration chart reading of 8910 gal. <br /> installed on the riser pipe to the inside, top corresponds to a dipstick measurement of 82". <br /> lip of the storage (A). <br /> Upper Tube Length -C+ A 5.) Dipstick number(X)= 82" <br /> U <br /> PP 9 - ( ) Tank diameter(Y) = 92" <br /> (Y)-(X) =(Z) (92"-82" = 10") <br /> YES Upper tube length is 6-1/2" plus the riser (Z)= 10" <br /> pipe measurement (A). <br /> 7.) (Z)-2"=C (10"-2"=8") <br /> Upper Tube Length=6-112"+ (A) C =8" <br /> NOTE: You must find the actual tank capacity 7.) Is 8" less than 6-1/2"? <br /> number that correlates to the 6-1/2"+ (A)depth <br /> for the station records. This number may also NO Measure the distance from the top of the <br /> be used for the purposes of calibrating an FSA-400 Face Seal Adaptor installed on the <br /> electronic tank level system, riser pipe to the inside, top lip of the storage <br /> tank and obtain measurement(A). <br /> ,-'Registered T.M.-Owens Coming Fiberglass Corporation Upper tube length = C +(A) <br /> 64 <br />