My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
ARCHIVED REPORTS
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
R
>
REPUBLIC
>
14720
>
2900 - Site Mitigation Program
>
PR0542085
>
ARCHIVED REPORTS
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/7/2020 3:18:39 PM
Creation date
5/7/2020 3:08:28 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2900 - Site Mitigation Program
File Section
ARCHIVED REPORTS
RECORD_ID
PR0542085
PE
2965
FACILITY_ID
FA0010858
FACILITY_NAME
SJC PUBLIC WORKS /UTILITY-FLAG CITY
STREET_NUMBER
14720
STREET_NAME
REPUBLIC
STREET_TYPE
St
City
LODI
Zip
95242
APN
05532009
CURRENT_STATUS
02
SITE_LOCATION
14720 Republic St
P_LOCATION
99
P_DISTRICT
004
QC Status
Approved
Scanner
LSauers
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
321
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
r <br /> 1 2.07 ELECTRICAL DESIGN <br /> 2 <br /> 3 A. The electric motors shall be 1.5 HP each, TEFC with a 1.15 service factor wired for 230V, <br /> a 1 phase, 60 Hz power and draw 2.6 amps at full load. <br /> 5 <br /> 6 B. The electrical system shall consist of a combination starter for each motor (disconnect <br /> r 7 switches), HOA switches, hour meter for each motor, control voltage transformer suitably <br /> 8 sized for all control wiring, and a panel mounted to the steel frame. <br /> 9 <br /> r to C. All wiring, switches, and panels shall be NEMA 4, watertight type. <br /> 11 <br /> 12 C. <br /> INTERCONNECTING PIPING/WIRING <br /> 13 <br /> 14 A. The motors shall be prewired to the control panel. <br /> 15 <br /> 16 B, The solenoid drain traps and control wiring shall be 115V, 1 phase, 60 Hz and be prewired <br /> r 17 from the panel transformer. <br /> 18 <br /> 19 C. The interconnecting piping between the compressors, aftercoolers, receiver, air filter, and <br /> 20 air dryer shall be prepiped. <br /> r 21 <br /> 22 D. The compressor package shall be shipped completely assembled such that the installer <br /> 23 only runs one power supply to the control panel and one air line from the air dryer and one <br /> r 24 condensate drain line. <br /> 25 <br /> 26 <br /> r27 PART 3: EXECUTION <br /> 28 <br /> 29 3.01 INSTALLATION <br /> 30 <br /> 31 The compressor, dryer, filters and accessories shall be installed in accordance with the <br /> 32 manufacturer's instructions and recommendations in the locations shown on the Drawings. <br /> 33 <br /> r35 <br /> 35 <br /> 36 <br /> 37 END OF SECTION <br /> 38 <br /> r <br /> r <br /> r <br /> r <br /> AIR COMPRESSOR <br /> 062794 119513 <br /> r <br />
The URL can be used to link to this page
Your browser does not support the video tag.