40 P,TankrK* y <br /> 8501 N MOPAC EXPRESSWAY,SUITE 400 <br /> AUSTIN,TEXAS 78759 <br /> (512)451-6334 <br /> FAX(512)459-1459 <br /> TEST DATE:09/17/08 WORK ORDER NUMBEF2258574 <br /> CLIENT:BP PRODUCTS NORTH AMERICA, INC. SITE-ARCO #06080, CC 18022649 <br /> COMMENTS <br /> ALL TESTS PASS. <br /> E-STOPS AND SHEARS OPERATING FINE. REPLACED 323 SENSOR IN 87 FILL SUMP. PUMPED APROX. ONE GAL. <br /> OF WATER FROM BOTH 89 STP SUMP AND TRANS. PIPING SUMP. BEGAN WATER ACCUMULATION IN ON SITE DRUM. <br /> E-TICKET# 9387861. <br /> REMOVED COTTER PIN FROM LOW POINT VAPOR SUMP SENSOR SLEEVE. <br /> PARTS REPLACED <br /> QUANTITY DESCRIPTION <br /> 1 POSITION SENSITIVE PAN/SUMP - 12 FT CABLE <br /> 87 FILL SUMP. <br /> HELIUM PINPOINT TEST RESULTS (IF APPLICABLE) <br /> ITEMS TESTED <br /> HELIUM PINPOINT LEAK TEST RESULTS <br /> Printed 09/26/2008 10:15 JGUTIERREZ <br />