Laserfiche WebLink
kip <br /> Line Leak Detector Test Data Sheet <br /> Station# ARCO 6080 Date: 8/24/10 <br /> Address: Street: 85 E LOUISE AVENUE <br /> City: LATHROP CA <br /> Test Information <br /> 1 2 3 4 5 <br /> Product Regular Mid rade Premium <br /> Manufacturer Red Jacket Red Jacket Red Jacket <br /> Model Mechanical Mechanical Mechanical <br /> Serial Number Not readable Not readable Not readable <br /> Full Operating Pressure (Psi) 36 38 32 <br /> Test Leak Rate(ml/min)(gph) 3 GPH 3 GPH 3 GPH <br /> Line Bleed Back(ml) <br /> Turbine Holding Pressure (Psi) 20 21 21 <br /> Metering Pressure (psi) 10 10 10 <br /> Open/Trip time Mech only 60 sec 60 sec 60 sec <br /> PASS or FAIL PASS PASS PASS <br /> Comments: <br /> Note: Pass=Leak detector reads leak and meters line. <br /> Fail=Leak detector did not read leak. <br /> This letter certifies that the annual leak detector tests were performed at the above referenced <br /> facility according to the equipment manufacturers procedures and limitations and the results as <br /> listed are to my knowledge true and correct. The mechanical leak test detector test pass/fail is <br /> determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Wayne Perry <br /> Technician Don Hicks Lie#300345 <br /> Signature <br />