SWRCB..lanuar% 2003 I agc 2. <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facilit\ is Not Equipped With Spill/Overfill Containment Boxes: El <br /> Spill/Overfill Containment Boxes are Present.but\\ere Not Tested: L] <br /> Test Method Dcvclopcd By: ❑ Spill Bucket Manufacturer � Indusu•\ titandnrd � Professional Engineer <br /> Other(Speco-) <br /> Test Method Used: ❑ Pressure F-1 Vacuum Hydrostatic <br /> Other(Specify) <br /> Test Equipment t Jscd: Equipment Resolution: <br /> I WN N H � Spill Box 1-REG 1-87 Spill Box 2-PLUS 2-89 Spill Box# 3-PREM 3-91 Spill Box <br /> I. <br /> Bucket Diameter: 10" 10" 10" <br /> Bucket Depth: 16" 16" 16" <br /> Wait time between applying <br /> pressure/vacuum/water and 5 MIN. 5 MIN. 5 MN. <br /> starting test: <br /> Test Start Time: 9:35 9:35 9:35 <br /> Initial Reading(RI ): <br /> 11" 11" 11" <br /> Test End Time: 10:40 10:40 10:40 <br /> Final Reading(RF ): 11" 11" 11" <br /> Test Duration: 60 MIN. 60 MIN. 60 MIN. <br /> Change in Reading(R F-RI ) 0" o" 0" <br /> Pass/Fail Threshold or PASS PASS PASS <br /> Criteria: <br /> Test Result: Pass 171 Fail IZI Pass E Fail [K]Pass F] Fail E]Pass D Fail <br /> Comments- (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> OPW SPILL BUCKET'S ON SITE. <br />