• HUNTER ENVIRONMENTAL SERVICES, INC. �" , ,'; �, FINAL TEST RESULTS <br /> 18350 MT. LANGLEY STREET, SUITE 1014" % ' TEST DATE: 4/8/88 <br /> FOUNTAIN VALLEY, CA 92708 <br /> 800-247-9014 BOO-247-2186 <br /> CUSTOMER ARCO �, �:4:, , �.N���r :0/5�'° LOCATION/IDENTIFICATION NO.: 6080 <br /> ADDRESS: _ <br /> LATHROP, CA <br /> TEST RESULTS SUMMARY <br /> --------------- LEAK LOKATOR RESULTS--------------------_ <br /> SYSTEM TANK SIZE WATER LEVEL ALR <br /> ----------------- <br /> NO. PRODUCT •GALLONS - --- --------- --------- ------- ------ <br /> DIA/MATE INCHES INCHES GPH CONCLUSION RECOMMENDATIONS <br /> ---------------------------- -------- ------ ------ --- ---------- ---------------- <br /> 1 S/U 12000 92/FG 0 141 +.036 TIGHT <br /> 2 U/L 12000 921FG 0 135 -.040 TIGHT <br /> PRODUCT LINES - HYDROSTATIC PRESSURE TEST RESULTS <br /> SYSTEM TYPE OF-----PUMP--- <br /> POUNDS POUNDS MINUTES PRODUCT PRODUCT CONCLUSION <br /> ---------- <br /> NO. PRODUCT REMOTE SUCTION APPLIED HELD HELD LOSS CC's LOSS GPH /RESULT <br /> ---------------------------------------------------------------------------------------------------------------- <br /> 1 S/U RED JACKET 50 48 10 PASS <br /> 2 U/L RED JACKET 50 49 10 PASS <br /> NOTE: On suction systems, NEVER put more than 15 psi on any pump system. <br /> DETAIL OF TEST RESULTS <br /> TEST TIME --LEAK-RATE--- <br /> TEMPERATURE ABSOLUTE CHECK <br /> --------------- ---- ---- <br /> SYSTEM TEST LEVEL CLOCK DURATION COMPENSATION LEAK RATE TEST <br /> NO. PRODUCT NO. (IN.) STATE (HR-MIN) CC/DIV CC/MIN DELTA of CC/MIN CC/MIN GPH Y/N <br /> ------------------------------------------------------------------------------------------------------------------- <br /> 1 S/U 1 141 10:30 :60 8.163 +51.232 +.095 +48.902 +2.33 +.036 N <br /> 2 U/L 1 135 2:20 :60 +7.362 +8.435 +.022 +10.991 -2.556 -.040 N <br /> *LEVEL - Inches from Tank Bottom to Test Level <br /> ALR - Absolute Leak Rate (Measured Leak Rate - Temperature Compensation) in Gallons Per Hour <br /> CONCLUSION - NFPA 329 criterion of +/- 0.05 GPA is used to certify tightness <br /> CERTIFICATION rn <br /> %LLArrDItU <br /> This is to certify that the above tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK <br /> LOKATOR according to all standard operating procedures. Those indicated as tight at full system meet the criterion <br /> established by the National Fire Protection Association Pamphlet 329 for Precision Testing. <br /> Tests Conducted and Certified By: Test Van No. 7 <br /> Team Manager: P. WHEELER <br /> Tank Testing Specialist: S. ANDERSON <br />