Laserfiche WebLink
EMERGENCY PUMP AND DISPENSER SHUT OFF CHECKLIST <br /> FACILITY # (00?)D DATE <br /> ADDRESS L w,sc- <br /> 1. Authorize one dispenser of each product at the ARCOmatic. Go to dispenser of authorized <br /> product and turn on the handle. <br /> 2. Turn emergency switch, independent of ARCOmatic switch, to stop position. Note: each <br /> emergency stop switch must be tested independently.. <br /> 3A. Tokheim Dispensers Only <br /> Check relays in (1) power centers and (2) turbine relay boxes to verify that they are open and <br /> that power to the turbines is off. <br /> Open turbine sumps and verify turbines are off. Note results below. <br /> 3B. Gilbarco &Wayne Dispensers Only <br /> Verify at least one dispenser of each product will shut off. Check turbine relay boxes to verify <br /> that they are open and that power to the turbines is off. <br /> Open turbine sumps and verify turbines are off. Note results below. <br /> 4. ARCOmatic Sites Only:--(NCR's do not have emergency stop switches on console.l <br /> Authorize one dispenser to verify that dispenser power shuts down and/or turbine power shuts <br /> down. Repeat procedure#4 for each dispenser and note results below. <br /> STOP SWITCH SHUTS DOWN COMMENTIREPAIRS <br /> TURBINE DISPENSER <br /> (Y/N) (Y/N) <br /> ARCOmatic P- <br /> OUTSIDE WALL Irk <br /> INSIDE STORE `I 5 �o Oiso F��$��� �o�• <br /> OTHER T <br /> 5. Turn emergency switch back to run position. <br /> 6. Put station back in operation. <br /> 7. Install turbine circuit breaker and emergency stop decals supplied by ARCO if necessary. -- <br /> CONTRACTOR C.�'�C h SIGNATURE u <br /> Comments: �� <br />