Laserfiche WebLink
f 1 <br /> 6ETTLER - RYAN INC. <br /> Comment#5: Three revised copies of the relevant pages of the Work Plan that reflects the <br /> correct overfill prevention method for the USTs. Sheet#F-1, section "Scope of Work" item F <br /> indicates drop tubes to shut off at 95% tank capacity, sheet#M.5.3.01, item#41 indicates a <br /> straight drop tube OPW Model#61T. Drawings on sheets#M.5.3.03 and M.5.3.04 shows <br /> straight drop tubes and sheet#M.5.3.04, section "Notes: UST Installation", item#15 indicates <br /> the use of an overfill alarm set at 90%. <br /> Response: Sheet F-1 item F has been modified to reflect using STRAIGHT DROP TUBE IN <br /> EACH TANK WITH AUDIBLE/VISUAL ALARM. Clouded for clarification and marked as "Item <br /> #5". It will match the details on sheet#M.5.3.01, M.5.3.03, and M.5.3.04. <br /> Comment#6: Three revised pages of the Work Plan that reflects the correct fuel product for <br /> the 10,000 gallon tank along with its associated piping connections and appurtenances for all <br /> tanks on sheets M.5.3.03, M.5.3.04, M.5.3.08, and M. 5.3.13. <br /> Response: Sheets M.5.3.03, M.5.3.04, M.5.3.08, and M. 5.3.13 have been modified to show <br /> the 10,000 gallon Diesel tank. Clouded for clarification and marked as "Item #6". <br /> Comment#7: Three revised pages of Site Plan Sheet T-1 section "Agency Contacts" to <br /> reflect correct CUPA information. The correct information can be found on the letterhead of <br /> this letter. <br /> Response: All the Agency Contacts on Sheet T-1 have been revised and clouded for clarity. <br /> Marked as "Item#7". <br /> Comment#8: Revised page 3 and 6 of the SJC EHD Application for UST installation Permit <br /> that lists each tank separately and its product stored. There should be a listing of 3 individual <br /> tanks. <br /> Response: Revised. Please see the attached, marked as "Item#8". <br /> Comment#9: Current copies of ICC Service Technician and ICC Installer's certificates and <br /> all manufacturer training certificates for each person that installs or tests any of the <br /> components that will be used in the installation of the entire UST system. <br /> Response: Provided. Please see the attached, marked as "Item#9". <br /> 6747 Sierra Court, Suite J • Dublin, CA 94568 • (925) 551-7555 • Fax (925) 551-7888 <br /> 3140 Gold Camp Drive, Suite 170 • Rancho Cordova, CA 95670 • (916) 631-1300 • Fax (916) 631-1317 <br />