Laserfiche WebLink
Wayne / Bennett CDIM Installation <br /> 1. Open the left-hand door of the TLS-350R console by unscrewing the left-top and left-bottom locking bolts. <br /> ti 2. To retain current programming,be sure that the ECPU board battery switch is set to"ON"(SWI in the closed position-see <br /> Figure 1).To avoid electrical shock or damage to components when accessing the battery switch,avoid touching any circuit <br /> components with your hand or any conductive tool. <br /> ti <br /> Battery Backup Switch(S1) <br /> Shown in On position(up) <br /> a,:des�ers�auw eP. <br /> Figure 1. TLS-35OR Console ECPU Board Battery Switch <br /> 3. Turn console power Off. <br /> 4. Avoid shorting high voltage across any component or module to the intrinsically safe section of the console.This could result in an <br /> explosion near the device. <br /> 5. Open the left-hand door of the console by unscrewing the left-top and left-bottom torx screws. <br /> 6. Remove the blank cover plate from an open slot in the communication compartment.Important Note:CDIMs can only be installed <br /> in slots 1,2,or 3 of the console's Comm Bay card cage(Figure 2). <br /> If your console has a snap connector which secures the cover plate in the card cage,pull it out and lift out the cover plate. <br /> If your console has"knockout"cover plates,open the printer door and insert a flat blade screw driver in the slot provided in the <br /> front of the cover plate you are removing and twist it to break the front set of metal securing tabs(Figure 2).Once the front tabs <br /> are broken,carefully rock the loosened end of the plate until the rear set of securing tabs break.Remove and discard the cover <br /> plate. <br /> 7. Slide the new Wayne or Bennett CDIM into the open slot(Figure 2)until the 24-pin female connector on the rear edge of the <br /> board seats in the 24-pin male connector on the motherboard.Do not apply excessive force when installing the module.With your <br /> thumb,push in the black retaining fastener on the end plate until it snaps into the hole in the card cage. <br /> 8. When you are finished,make sure any unused slots in the comm cage have a blank end plate installed. <br /> 9. Check that the three CDIM RJ45 jacks are accessible through the slot opening at the bottom of the console once the CDIM is <br /> installed. <br /> 5 <br />