Laserfiche WebLink
C err 9Wria . i --STC <br /> Matrix Spike/ Matrix Spike Duplicate/ LCS <br /> ANALYSIS DATE: 8/17/2018 Unit : mp/L(ppm) <br /> Analysis Spk.Sample LCS LCS LCS Sample Spike MS % R6c MW Rec % RPD <br /> I i+ <br /> ID CONC. %Rec. STATUS Result Conc. MS MSB <br /> Arsenic(As) 180814-7 --- 5.00 102 PASS 0.318 5.00 5.13 96% 5.20 98% 1% <br /> Chromium(Cr) 180814-7 5.00 99 PASS 1.60 5.00 6 45 97% 51 98% 10/0 <br /> Lead(Pb) 180814-7 5.00 I 1I F PASS 0.450 5.00 3.87 68% s 9 69% <br /> ANALYSIS DATE: 8/13/2018 <br /> Analysis Spk.Sample LCS LCS LCS Sample Spike M % Rec MSD % Rec % RPD <br /> ID CONC. %Rec. STATU Result Conc. MS SD <br /> Mercury (Hg) 180809-5 0.0125 96 PASS 0 0.0125 0.0120 96% 0.0120 96% 0% <br /> MS/MSD Status: <br /> Analysis %MS %MSD %LCS %RPD <br /> Arsenic(As) PASS PASS PASS PASS <br /> Chromium(Cr) PASS PASS PASS PA5.S <br /> Lead(Pb) FAIL FAIL* PASS PASS ANALYST: <br /> Mercury(Hg) I PASS PASS PASS PASS <br /> Accepted Range 75- 125 75- 125 85 - 115 0 - 20 FINAL REVIEWER: q i'D <br /> "=Fail due to matrix interference ' <br /> Note:LCS is in control therefore results are in control <br />