Laserfiche WebLink
A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> GSG GAS & MART 701 E DR MARTIN LUTHER KING JR BLVD, June 29, 2020 <br /> Other Violations <br /> 2010 1 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 103 HSC 25292.2, 25299.30 Failure to submit and maintain complete and current financial responsibility documents. <br /> OBSERVATION: Financial responsibility documents have not been submitted to the EHD. The most recent <br /> financial responsibility documents in CERS are dated 02/17/2019. <br /> REGULATION GUIDANCE: Current financial responsibility documents are required to be submitted annually. <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS) at <br /> http://cers.calepa.ca.gov/, and upload the required documents. <br /> This is a minor violation. <br /> 306 CCR 2630(d), 2641(a) Monitoring equipment is not installed or maintained to detect a leak at the earliest <br /> opportunity. <br /> OBSERVATION: The 87 STP sensor was raised approximately 1.5 inches off the lowest point of the sump and not <br /> located to detect a leak at the earliest opportunity. <br /> REGULATION GUIDANCE: Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> CORRECTIVE ACTION: The sensor was relocated to the lowest point of the sump by the service technician. <br /> Ensure that all monitoring equipment is maintained and located to detect a leak at the earliest opportunity. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> 315 HSC 25291(e)Water in secondary containment not removed, analyzed, and properly disposed of (pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the 87 STP sump. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed the liquid from the 87 STP sump. Ensure that all sumps <br /> and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> FA0002512 PR0231059 SCO01 06/29/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />