Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> ,jw Tanknology Line Leak Detector Test <br /> Work Order: 2344049 Date : 2/6/2020 <br /> Site Name / ID : 7 ELEVEN 35355 / 35355 <br /> Address : 3202 W HAMMER LANE ( W136) Zi 95209 <br /> City : <br /> STOCKTON State : CA p <br /> Tank ID T1 : T2 : T3 : <br /> Product RUL PUL Diesel <br /> Product Line 1 1 1 <br /> Tested From 5 5 7 <br /> Existing / New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model FE Petro MLD FE Petro MLD Vaporless LD-2000 <br /> Serial No . UNREADABLE 02070690 05071049 <br /> Pump Operating Pressure (psi ) 29 . 00 31 . 00 33 . 00 <br /> alibrated Leak (mllmin) 189 . 0 189 . 0 189 . 0 <br /> alibrated Leak (gph) 3 . 00 3 . 00 3 . 00 <br /> Holding PSI 29 . 00 31 . 00 33 . 00 <br /> ` NIA for Electronic LD's <br /> Resiliency (ml ) 150 . 00 155 . 00 150 . 00 <br /> ' NIA for Electronic LD' s <br /> Metering PSI 11 13 14 <br /> ' NIA for Electronic LD' s <br /> pening Time (sec) 5 6 6 <br /> ' NIA for Electronic LD's <br /> est Results Pass Pass Pass <br /> Technician Comments : <br /> Eb 64 <br /> EWR® NMENTAb 6 0 H <br /> DEPART AD Y , <br /> Technician Name : Jesus Saldivar Certification # : 115237 <br /> Expire Date : 1 /27 /2022 <br /> Technician Signature : `°"6 44- <br /> Environmental Compliance for Petroleum Systems <br /> © 2020 Tanknclogy Inc., Austin, Tx. All rights reserved. tanknology.com <br />