Anoxic Mix Pump <br /> Sized Based on 0.5 HP per 1,000 cf <br /> 3,500 gal/ 7.48 gal/cf=467.9 cf <br /> 467.9 cf/ 1,000 cf x 0.5 HP = 0.47 HP <br /> Pump HP Provided =0.5 HP <br /> Anoxic Mix Pump (1) = 0.5 HP <br /> MLSS Recycle Pump <br /> Sized Based on 100%ADF <br /> 6.25 gpm x 100% = 6.25 gpm <br /> Recycle Pump Provided = 10 gpm @ 25' TDH <br /> Recycle Pump (1) = 0.5HP <br /> SUMMARY OF PLANT DESIGN <br /> Influent Average Daily Flow = 7,167 gpd <br /> Design Flow= 9,000 gpd <br /> Package Plant Chamber Required Size Actual Size Safety Factor <br /> EQ Chamber 3,600 gal 4,350 gal 1.21 <br /> Anoxic Chamber 3,150 gal 3,500 gal 1.11 <br /> Aeration Chamber 8,977 gal 13,125 gal 1.46 <br /> Clarifier Overflow 9 sf 68 sf 7.55 <br /> Clarifier Weir 0.45 If 8 If 17.7 <br /> Sludge Chamber 2,019 gal 2,975 gal 1.47 <br /> Chlorine Chamber 375 gal 400 gal 1.07 <br /> De-Chlor Chamber 312 gal 348 gal 1.12 <br /> EQ Blower 5 cfm 22 cfm 4.4 <br /> Aer/Sludge/Airlift Blower 48 cfm 55 cfm 1.15 <br /> Page 11 of 11 <br />